Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
Box
:
Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung , PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
max. 60 °C
Operating pressure
:
atmosphärisch
media density
:
ρ ≥ 0,6 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24…230 V AC/DC
Power consumption
:
≤ 2 W
Output
Output contact
:
2 potentialfreie Wechselkontakte
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 5 A AC / 5 A DC
Switching capacity
:
max. 750 VA / 90 W
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
CE marking
:
siehe Konformitätserklärung
TK-309
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
07
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
Accessories
:
R/I-Wandler TK-101
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
Protection class EN60529
:
IP 65
connection thread
:
G1" | G1¼" | G1½"
Union nut
:
G2¾" | S 100x8
Operating temperature PE / PVC
:
atmospheric
Operating temperature PPH
:
90°C
Operating temperature PTFE
:
100°C
Operating pressure
:
atmospheric
Resistance value of line monitoring
:
22 kΩ / 100 kΩ