Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Polyester
Box
:
Aluminium
Box
:
Polyethylen
Box
:
Kabel
Box
:
Stecker
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
atmosphärisch; PP max. 90°C
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
Protection class EN60529
:
IP 65
connection thread
:
G1" | G1¼" | G1½"
Union nut
:
G2¾" | S 100x8
Operating temperature PE / PVC
:
atmospheric
Operating temperature PPH
:
90°C
Operating temperature PTFE
:
100°C
Operating pressure
:
atmospheric
Resistance value of line monitoring
:
22 kΩ / 100 kΩ
Software and USB kit for configuration & evaluation
Properties
details
:
folgen
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
Box
:
Ex-Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung, PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ZCS-5000
Self-contained CO2 sensor ZCS-5000 in small housing with warning horn
stand alone CO2 sensor for measuring and monitoring carbon dioxide concentration in ambient air.
Properties
Housing
:
Kunststoff
Power supply 24V
:
24V DC | 230V
Measuring element and parameter
Measuring principle
:
optisch, NDIR
measuring grid
:
2 sec.
Accuracy
: