Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
Box
:
Ex-Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung, PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
DTS-CAN
Flexible, digital pressure and temperature sensor with CAN bus
Media-immersed, flush-mounted, stainless steel pressure-temperature sensor with CAN bus
Properties
Operating voltage
:
9...27V
Power consumption
:
35 mA typ (50 mA max)
Dimensions
:
75x22 mm
Process connection
:
G 1/4“
Measuring range
Temperature
:
-20…+100 °C
ltdata.Druck
:
(-1) 0…100 bar
ltdata.AbweichungDruck
:
max +/- 0,5 % FS @ 0-10°C
ltdata.
:
MTA
Mechanical tank level indicator
The tank level indicator is a mechanically actuated indication operating "on the spot”. It permits a high degree of safety and flexibility thanks to separate points of measurement and indication.
Properties
Tank connection
:
Flansch ab DN 80 (Sonderanschlüsse auf Wunsch)
Material
:
siehe Maßbild
Material Tube
:
PVC, transparent | Ø 50 x 1,8 | Ø 63 x 3,0
Operating temperature
:
–20...+60 °C
Operating pressure
:
atmosphärisch
Material Float
PPH
:
Ø 70 mm 460 g
PVC
:
Ø 70 mm 455 g
PPH
:
Ø 40 mm 370g
PE
:
Ø 70 mm ca. 450 g
Material Rope
PPH
:
(rot, Ø 2 mm) ~ 2 g/m
Polyester
:
(bunt, Ø 2 mm) ~ 4 g/m
PTFE
:
(weiss, Ø 3 mm) ~ 10 g/m
Ex-BK
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
–20...+120 °C
Wire cross-section max.
:
1,5mm²
Switching point distance between two contacts
:
min. 40 mm
Switching hysteresis
:
ca. 10-15 mm
Dimensions
:
80 mm x 75 mm x 57 mm
Material
Housing
:
Aluminium
Mounting clip
:
V2A
Rivet
:
V2A
Screw connection
:
M 20 x 1.5, V2A
Weight
BK-390-50
:
137 g
BK-390-63 / BK-380
:
140 g
Switching contact
Switching voltage
:
24...250 V AC/DC
Switching current
:
20 mA...6 A AC/DC
Switching capacity(min.)
:
max. 500 VA, 60 W
Switching capacity(max.)
:
min. 2 VA/W
SG2420
Supply unit SG2420 for flow sensor
The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
Housing
:
Kunststoff
Protection class
:
IP00
Ambient temperature
:
-20…+60°C
Supply voltage
:
24V DC +20% / -10%
Our application engineers advise you