The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
clamp
:
IP20
Housing
:
IP40
Technical Data
Operating temperature
:
-20...+60 °C
Storage temperature
:
-30...+80 °C
Output contacts
:
potentialfrei
Switching voltage
:
min. 5 V, max. 250 V AC / 150 V DC
Switching current
:
min. 5 mA, max. 5 A AC / 5 A DC
Switching capacity
:
min. 300 mW, max.100 VA / max. 50 W
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
Box
:
Ex-Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung, PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
TSR-CAN-03
CANopen transmitter for temperature measurement in media
High-quality stainless steel transmitter for precise temperature measurement in all stainless steel-compatible media
Measurement parameters
Measuring range
:
-40…+80 °C (optional +150°C)
deviation
:
± 0,3 K (-40…+80 °C)
Measuring element
:
Halbleiter
measuring resolution
:
10 Bit
measuring grid
:
ab 5 ms
ElectricalConnection
CAN protocol
:
CANopen 2.0 A, nach ciA DS 404
Physical Layer
:
nach DIN 11898
Operating voltage
:
12…27 V ±20 %
Operating conditions
Operating temperature
:
-40...+80 °C
Storage temperature
:
-40°C...+120°C
Shock resistance
:
30g, Dauer: 14 ms bei Raumtemperatur
Vibration resistance
:
10g bei 20 bis 1000 Hz
Our application engineers advise you
personally, comprehensively and professionally!