ZMF-100-IR
gas detector with 4...20mA signal output
industrial CO2 sensor ZMF-100-IR with a measuring range of up to 50,000ppm
Product features
- Measuring principle : optisch, NDIR (nicht-dispersive Infrarot-Absorptionsmessung)
- Operating voltage : 24 V DC / 100 mA
- Heating time : ca. 5 min
- Response time : ca. 30 s
- Repeatability : +/- 1%
- Housing : Aluminium (rot) IP54
- Weight : ca. 500g
- Shaft range : 4,27 - 4,35 µm (4270-4350 nm)
- Gas ingress : per Diffusion
ambient conditions
- Operating temperature range : -10...+50 °C
- Storage temperature range : -40...+100 °C
- RelativeHumidity : 15..95 %
- Air pressure : 900...1100 hPa
KST-20 Calima
Climate control for automatic & controlled dehumidification, ventilation and cooling of rooms
The KST-20 Calima climate control system with aH-Controlled technology for ventilation and dehumidification for all types of private, commercial and industrial rooms. With the operating modes for living room ventilation and room dehumidification, the KST-20 Calima can be used flexibly in almost all living, working and industrial areas.
Specifications
- measuring range (Humidity) : 0…100% rF,
- Measuring accuracy (humidity) : ±2%
- measuring range (Temperature) : -40…+80°C
- Measuring accuracy (temperature) : ±0,2°C
- Signal output : I2C
- Connections for actuators : Zwei Steuer- und Schaltausgänge für Zuluft- und Abluftelemente
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 140x140x46 mm
Connection options
- Dehumidification : Einstufige Lüftungsventilatoren
- Room dehumidification / living space ventilation : Zweistufige Lüftungsventilatoren
- Living space ventilation / Dehumidification : Drehzahlgesteuerte Ventilatoren 0…10 V DC
Operating conditions
- Temperature : 0...50 °C
- RelativeHumidity : 85 % nicht kondensierend
- EMV/ESD : EN50082-1/2
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
ZT-F
Reliable OEM pressure sensor with many customisation options (0...0,6 to 0…1.000 bar)
Can be used with all media and applications compatible with stainless steel
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
ER-214
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
- Weight : ca. 150 g
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
Output
- Contacts : 1 potentialfreie Wechselkontakte pro Kanal
- Switching voltage : min. 5 V | max. 250 V AC | max. 150 V DC
- Switching current : min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
- Switching capacity : min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
- Working / Idle current : umschaltbar
- overvoltage category : EN 61010-1 Kategorie III
PVG-399
PVC weight with magnet insert and eyelet for cable fixing
for actuating monostable and bistable contacts
Variants
- 32 : Außen Ø 25 mm x 175 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 32 u. 34 mm bis 6m Länge
- 37 : Außen Ø 30 mm x 170 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 40 mm bis 6m Länge
- 40 : Außen Ø 40 mm x 110 mm ca. 175g, geeignet für Rohraußen Ø 50 mm bis 6m Länge
- 4012 : Außen Ø 40 mm x 110 mm ca. 300g, geeignet für Rohraußen Ø 50 mm bis 12m Länge
- 4016 : Außen Ø 40 mm x 110 mm ca. 360g geeignet für Rohraußen Ø 50 mm bis 16m Länge
- 50 : Außen Ø 50 mm x 130 mm ca. 255g, geeignet für Rohraußen Ø 63 mm bis 6m Länge
- 5012 : Außen Ø 50 mm x 130 mm ca. 300g geeignet für Rohraußen Ø 63 mm bis 12m Länge
- 5016 : Außen Ø 50 mm x 130 mm, ca. 360g, geeignet für Rohraußen Ø 63 mm bis 16m Länge
T203
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
tdata.
- connection : Polyesterdose | Aluminiumdose
- Protection class : IP 65 Dose
- Guide tube : Edelstahl 1.4571, Ø 15 mm
- Guide Tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- F-Contact : 1/12 kΩ
- Switching current : 1A, 2A ( nur mit Schirmung)
Float types
- float type 05 : Dichte: 0,81 g/cm³ | 110 mm Abstand
- float type 06 : Dichte: 0,67 g/cm³ | 135 mm Abstand
Number of contacts
- Changeover contact : 5x
- normally open : 6x
- Normally closed contact : 4x
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
VS-D250
Transmitter for ViscoScope viscosity sensors
Maximum flexibility for an optimal choice of measuring instrument: The VS-D250 transmitter is compatible with all ViscoScope® sensors of the types VA-100 and VA-300.
Properties
- Output card socket : 2
- External input : 0/4…20 mA | 0/2…10 V DC
- Power supply : 24V DC, 12 W
- Dimensions : 142 x 106 x 73 mm (L x B x H)
- Front : RS232, MODBUS RTU (Standard)
Display and Operation
- Lines : 4
- Pages : 2
- Character set : alphanumerisch
- Buttons : 3 (front)
Alarms
- system function :
- sensor diagnosis :
- Coil Temperature :
- 2 configurable LEDs :
optional outputs
- 0/4…20mA | 0/2…10V DC (active) :
- RS232 | RS485 :
- 2 SPDT-Relays: RS232 | RS485 :
Filter
- Moving average (200 measured values) :
T205 PP
Magnetic immersion probes made of PP
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 65
- Number of floats : 1x Typ 12 | 1x Typ 13
- connection cable : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : max. 60 °C
- Operating pressure : drucklos
- Number of contacts : 1x Schließer / Öffner
- Switching current : 1 A
- Switching voltage : 250 V AC
- Switching capacity : 50 W/VA
Float type
- Type 12 : Zylinder PP 19 mm Ø | Dichte 0,93 g/cm³
- Type 13 : Zylinder PP 25 mm Ø | 0,68 g/cm³
ES-Serie
electronic safety switching device
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
AD-310
programmable Digital Display
The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel : IP 65
- Operating temperature : – 20...+ 60 °C
- nominal voltage : Weitbereichsnetzteil; 20 V DC ... 230 V AC
- Power consumption : max. ca. 3 VA
- Output contact : 2 Schließer / NO
- Switching voltage : max. 250 V AC, 300 V DC
- Switching current : max. 3 A , DC min. 30 mA
- Switching capacity : max. 50W, 100 VA
- Unregulated auxiliary voltage source : 15...20 V DC / 20 mA
- Display : LED 14 mm, 5-stellig
- Dimensions : 96x48x100 mm
- Weight : ca. 200 g
- Panel cut-out : H:45+0,6mm, B:92+0,8 mm
Equipment
- Measuring input current : 0(4)...20 mA DC
- Measuring input voltage : 0(2)...10 V DC
- Measuring input Potentiometric voltage divider : 1...100 kΩ
- Display : LED 14 mm, 5-stellig
- operation : Folientasten
- Display range : -19999...32000
- data backup : EEPROM
- measurement uncertainty : ±1 % oder ±1 Digit
- analogue output : 0 (4)...20 mA
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
- Box : Ex-Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung, PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
- Switching time : ca. 20 ms
ELH 230 V
Hanging electrode as leakage probe 24...230 V AC/DC
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
ÜTA-32
Overfuelling indicator
The top-mounted tank indicator is a mechanically operated, on-the-spot indicator. The liquid level in the tank located below the indicator is determined proportionately to the filling level and is indicated. Control of the level is easily achieved through the installation of switching contacts. The switching points for level control can be steplessly adjusted, on-the-spot and at any time.
Properties
- connection : G 1” (andere Gewinde auf Anfrage)
- max.length guide tube : siehe Diagramm
- Operating temperature : atmosphär. Bedingungen
- Operating pressure : atmosphär. Bedingungen
- media density : siehe Eintauchtiefe
- Number of contacts : beliebig
- Contact load : max. 10 VA, max. 230 V AC
- Length : max. 1750 mm
Material
- Sight tube : PVC transparent
- connection : PVC-Verschraubung mit PTFE-Stangenführung
- Guide rod : Edelstahl, Titan, Hastelloy B, Hastelloy C oder PVCRohr
- float : PE / PP
QFSK-2X
Stainless steel float switch combination
Float switch combinations QFSK for level monitoring & level control with maximum and minimum contact sensor.
Properties
- Protection class EN60529 : IP 68
- Material Float : VA 1.4571
- Material hose : Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
- rod length : max. 5 m
- Number of floats : bis 5
- Operating temperature : max. + 150 °C
- media density : ρ ≥ 0,8g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Switching voltage : 4...250 V AC/DC
- Switching current : 1 mA ...1 A
- Switching capacity : max. 1A, 60 VA/60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. + 20° / – 20°
- Ex-protection : optional; IBExU10ATEX 1089
- Operating pressure WFSK-25 : max. 15 bar
- Operating pressure QFSK-26 : max. 6 bar
Our application engineers advise you personally, comprehensively and professionally!