The FDL400 "Flow Data Logger 400" measuring device is suitable for measuring the flow of water and wastewater in fully or partially filled sewers or pipes of various geometries.
Properties
Housing
:
Aluminium
Protection class
:
IP30
Dimensions
:
197 x 153 x 37,5mm (B x H x T)
Temperature range
:
0 – 50°C
Supply voltage
:
24V DC +/-20%
Power consumption
:
120mA – 220mA
Reverse polarity protection
:
✓
Display
:
4x20
Outputs
analog 0(4)–20mA
:
3x
digital
:
4x
fixed for alarm
:
1x
free configurable
:
3x
display of measured value
Flow velocity
:
Filling level
:
flow
:
flow rate
:
TK-304
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class Socket
:
IP 65
Float type
:
03, 04, 09
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar (Kugel) max. 15 bar (Zylinder)
Resolution
:
7,5 mm | 10 mm
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 03
:
0,75 g/cm³
Type 04
:
0,65 g/cm³
Type 09
:
0,76 g/cm³
T-200.L 24V
Leakage probes with general building authority approval
The leakage probes T-200.L (24 V) are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
Box
:
Polyesterdose (PO)
Head
:
Polyethylenanschlusskopf (PE)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung , PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
max. 60 °C
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24 V DC (24...30 V DC)
Power consumption
:
≤ 1 W
Output
Output contact
:
1 potentialfreier Wechselkontakt
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 3 A AC / 3 A DC
Switching capacity
:
max. 750 VA / 90 W
Optocoupler
Switching voltage
:
max. 30 V
Switching current
:
max. 100 mA
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
PVG-399
PVC weight with magnet insert and eyelet for cable fixing
for actuating monostable and bistable contacts
Variants
32
:
Außen Ø 25 mm x 175 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 32 u. 34 mm bis 6m Länge
37
:
Außen Ø 30 mm x 170 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 40 mm bis 6m Länge
40
:
Außen Ø 40 mm x 110 mm ca. 175g, geeignet für Rohraußen Ø 50 mm bis 6m Länge
4012
:
Außen Ø 40 mm x 110 mm ca. 300g, geeignet für Rohraußen Ø 50 mm bis 12m Länge
4016
:
Außen Ø 40 mm x 110 mm ca. 360g geeignet für Rohraußen Ø 50 mm bis 16m Länge
50
:
Außen Ø 50 mm x 130 mm ca. 255g, geeignet für Rohraußen Ø 63 mm bis 6m Länge
5012
:
Außen Ø 50 mm x 130 mm ca. 300g geeignet für Rohraußen Ø 63 mm bis 12m Länge
5016
:
Außen Ø 50 mm x 130 mm, ca. 360g, geeignet für Rohraußen Ø 63 mm bis 16m Länge
Our application engineers advise you