Evaluation unit with 4 limit contacts (NO-contacts)
The TK-315 limit comparator can be used in conjunction with our TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output signal for level control/measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99 mm
Dimensions housing type C
:
22,5 x 114,5 x 114 mm
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
4 Schließerkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff mit LCD-Anzeige (oponal)
Overpressure
:
1,2* (1,5*) x Nenndruck
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Signal output selection
:
0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
Pressure range
:
5…1.000 bar
Operating conditions
Operating voltage
:
14...28 VDC ± 10 %
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
Connections
Electrical connection
:
Schraubklemme im Gehäuse
Process connection
:
G1/4" (andere auf Anfrage)
T-200.L 24V
Leakage probes with general building authority approval
The leakage probes T-200.L (24 V) are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
Box
:
Polyesterdose (PO)
Head
:
Polyethylenanschlusskopf (PE)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung , PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
max. 60 °C
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24 V DC (24...30 V DC)
Power consumption
:
≤ 1 W
Output
Output contact
:
1 potentialfreier Wechselkontakt
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 3 A AC / 3 A DC
Switching capacity
:
max. 750 VA / 90 W
Optocoupler
Switching voltage
:
max. 30 V
Switching current
:
max. 100 mA
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
QFSK-2X
Stainless steel float switch combination
Float switch combinations QFSK for level monitoring & level control with maximum and minimum contact sensor.
Properties
Protection class EN60529
:
IP 68
Material Float
:
VA 1.4571
Material hose
:
Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
rod length
:
max. 5 m
Number of floats
:
bis 5
Operating temperature
:
max. + 150 °C
media density
:
ρ ≥ 0,8g/cm³
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Ex-protection
:
optional; IBExU10ATEX 1089
Operating pressure WFSK-25
:
max. 15 bar
Operating pressure QFSK-26
:
max. 6 bar
T-200.L
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Our application engineers advise you
personally, comprehensively and professionally!