Cart
product added to request
XR-4x0 | XR-4x1 configure
T-200.L Ex configure
T203 configure
ELH 24 V configure
HE configure
EF2…5 24V configure
EFV2 24V configure
TK-307-0 configure
TK-32X configure
KST-20 Calima configure
ES-20 configure
T-20x.F 230V configure
T-200.F Ex configure
XR-4x0 | XR-4x1
Electrode relay with ATEX
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
T205-0.F
Ex area zone 0 (category 1)
The magnetic immersion probes T20... are used to detect fill level limit values in containers for liquid media, where an explosive atmosphere of zone 0 (cat. 1) is present in the gas space above the liquid and Ex zone 1 (cat. 2) is present outside the container, in the area of the junction box.
Properties
- Protection class EN60529 cable : IP 68
- connection cable : max. 10 Meter PUR
- Sliding tube length : Max. 6000 mm
- Operating temperature : max. 120 °C
- F-Contact : 1 / 12 kΩ
Float
- Stainless steel ball 44 mm Ø : max. 15 bar | 0,60 g/cm³
- Stainless steel cylinder 27 mm Ø : max. 10 bar | 0,78 g/cm³
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
- Box : Ex-Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung, PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
- Switching time : ca. 20 ms
T203
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
tdata.
- connection : Polyesterdose | Aluminiumdose
- Protection class : IP 65 Dose
- Guide tube : Edelstahl 1.4571, Ø 15 mm
- Guide Tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- F-Contact : 1/12 kΩ
- Switching current : 1A, 2A ( nur mit Schirmung)
Float types
- float type 05 : Dichte: 0,81 g/cm³ | 110 mm Abstand
- float type 06 : Dichte: 0,67 g/cm³ | 135 mm Abstand
Number of contacts
- Changeover contact : 5x
- normally open : 6x
- Normally closed contact : 4x
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
ELH 24 V
Hanging electrode as leakage probe 24 V DC
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
HE
Pendant electrodes – single, multiple
suitable for high tanks, wells and sewers
tdata.AnschlussmitDose
- Protection class EN60529 : IP 54
- connection thread : G 2”
tdata.AnschlussohneDose
- Protection class EN60529 : IP 67
- connection thread : n.a. / G 2”
Material
- electrode body : PVC, PTFE, PPH
- Screw connection : PVC, PTFE
- Cable : PVC, PTFE
- electrode rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
Operating temperature
- ltdata.HE-PVC : 60 °C
- ltdata.HE-PTFE : 150°C
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (oponal)
- Overpressure : 1,2* (1,5*) x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
- Pressure range : 5…1.000 bar
Operating conditions
- Operating voltage : 14...28 VDC ± 10 %
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : G1/4" (andere auf Anfrage)
EF2…5 24V
Conductive electrodes with and without 24 V DC direct connection
The conductive electrodes EF2...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
DSM2420
Sensor for simultaneous measuring flow velocity and filling level
The DSM2420 sensor is a combined sensor for simultaneous measuring flow velocity and level in open or accessible closed channels of all types and shapes.
Properties
- Dimensions : 180 x 48 x 36,5 mm ( L x B x H )
- Weight : ca. 1,5 kg
- Protection class : IP68
- Cable length (standard) : 15 m
- Bending radius : > 10 x D (Kabeldurchmesser 6,25mm) = > 62,5mm
- Temperature range : 0°C ... 50°C
- Mounting shoe material : V2A 1,5mm
Certificates
- EX / ATEX : IBExU 04 ATEX 1256
Measuring principle
- Flow velocity: Ultrasonic Doppler :
- Filling level: Differential pressure :
Flow velocity
- Measuring range : 0,01 - 4 m / s
- Measuring accuracy : +/- 5 % vom Momentanwert im Kanal
- Temperature drift : 0,1% / °C ( Meßspanne )
- Temperature drift : 0,05% / °C ( Nullpunkt )
- Output signal : 4 - 20 mA
Filling level
- Measuring ranges : 0 –1 m ; 0 – 2 m ; 0 – 4 m
- Measuring accuracy : < 0,2% v.E. Summe aus Nichtlinearität, Hysterese und Wiederholbarkeit
- Temperature drift : 0,005% / °C v.E. Meßspanne
- Temperature drift : 0,005% / °C v.E. Nullpunkt
- Material : Al2O3 (96%) aktive Fläche
- Output signal : 4 – 20 mA
- Zero point : norm 4 mA ( +/- 3 % )
EFV2 24V
adaptive conductive electrodes with and without 24 V direct connection
The conductive electrode EFV2 is approved by the "DIBt" as an overfill prevention device for liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- connection thread : G2"
- Union nut : G2¾", S 100x8
- Material Screw connection : PE, PVC, PPH, PVDF
- Material Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal, Kohlestifte
- Operating temperature : PE, PVC: atmosphärisch PPH : 90 °C, PVDF: 100 °C
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ je nach Ausführung
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PVDF : 100 °C
Technical specifications electronic part
- Operating temperature : –20...+85 °C
- Storage temperature : –30...+85 °C
- nominal voltage : 24...30 V DC
- Power consumption : max. 2 W
- Switching voltage : max. 230 V AC / V DC min. 5 V DC (CMOS-Relais)
- Switching current : max. 0,12 A AC / A DC min. <1 mA
- Switching capacity : max. 25 VA / W
- Sensitivity : 3k … 100 kΩ
TK-307-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
General data
- Connection aluminium box : H30 x B50 x T45 mm
- Connection polyester box : H56 x B80 x T75 mm
- connection cable : 1000 mm PUR blau
- Protection class Socket : IP65
- Material Sliding tube : VA 1.4571
- Material of the angle fastening : VA 1.4408
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm
- Mounting : 2 Schlauchschellen
- Accessories : R/I-Wandler TK-101
TK-32X
Luminous Row Displays
Luminous row displays of type series TK-320...TK-322 are used for visually displaying process states such as filling levels.
Type
- TK-320 : Schaltschrankeinbaugehäuse 24 x 96 mm
- TK-321 : Schaltschrankeinbaugehäuse 24 x 96 mm
- TK-322 : 19” Karteneinschub 7 TE, 3 HE
Properties
- Protection class EN60529 : IP 52
- Operating temperature : – 20 °C...+60 °C
- nominal voltage : 24 V DC...230 V AC
- Input : 0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
- Output : 4...20 mA | Bürde max. 500 Ω
- Relay : 2 x Umschalter max. 230 V | min. 5 V | max. 3 A | min 1 mA
Display
- Number of LEDs : 33 (rot/grün); 32 (TK-322)
- Resolution : ca. 3,5 %
- Error : ± 1 LED
- connection : Schraubklemmen
- connection TK-322 : Steckerleiste
- Input : 0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
- Output : 4...20 mA | max. load 500 Ω
- Relay(2xSwitch) : max. 230 V | min. 5 V
- Relay(2xSwitch) : max. 3 A | min. 1 mA
KST-20 Calima
Climate control for automatic & controlled dehumidification, ventilation and cooling of rooms
The KST-20 Calima climate control system with aH-Controlled technology for ventilation and dehumidification for all types of private, commercial and industrial rooms. With the operating modes for living room ventilation and room dehumidification, the KST-20 Calima can be used flexibly in almost all living, working and industrial areas.
Specifications
- measuring range (Humidity) : 0…100% rF,
- Measuring accuracy (humidity) : ±2%
- measuring range (Temperature) : -40…+80°C
- Measuring accuracy (temperature) : ±0,2°C
- Signal output : I2C
- Connections for actuators : Zwei Steuer- und Schaltausgänge für Zuluft- und Abluftelemente
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 140x140x46 mm
Connection options
- Dehumidification : Einstufige Lüftungsventilatoren
- Room dehumidification / living space ventilation : Zweistufige Lüftungsventilatoren
- Living space ventilation / Dehumidification : Drehzahlgesteuerte Ventilatoren 0…10 V DC
Operating conditions
- Temperature : 0...50 °C
- RelativeHumidity : 85 % nicht kondensierend
- EMV/ESD : EN50082-1/2
ES-20
Pressure limiter | Pressure monitor | Safety pressure limiter | Pressure regulator | electronic safety switching device
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
Connections
- Process connection Relative pressure (internal thread) : G ¼“
- Process connection differential pressure (internal thread) : G ⅛“
- Analogue current output : 1 x 4...20 mA
- Digital inputs/outputs (configurable) : 2 x Alarm / 1 x Alarm & 1 x Fernentriegelung
Measuring range relative pressure
- Nominal pressure (variable selectable) : -1...500 bar
- Overload pressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Setting accuracy : 0,1 % vom Nenndruck
Measuring range differential pressure
- Nominal pressure : 0...1 mbar 0...10 mbar 0...50 mbar 0...100 mbar 0...250 mbar 0...1.000 mbar
- Overload pressure : 10 x Nenndruck
- Bursting pressure : 15 x Nenndruck
- Setting accuracy : 0,1 % vom Nenndruck
T-20x.F 230V
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Polyester
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : max. 80°C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
T-200.F Ex
Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Ex-Polyester
- Box : Ex-Aluminium
Properties
- Protection class EN60529 : IP 65
- connection thread : G2"
- Union nut : G 2¾"
- Guide tube length : max. 6 m
- Operating temperature : -20…+60 °C
- Operating pressure : max. 6 bar je nach Ausführung
- media density : ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- Ex-protection : siehe Baumusterprüfbescheinigung
- CE marking : siehe Konformitätserklärung
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!