Cart
product added to request
KG-2XX configure
TK-301 PTFE configure
ES-21 configure
Ex-BK configure
T-20x.F 230V configure
QFS-1X configure
QFSK-2X configure
KG-2XX
Capacitiv Limit Switch
Capacitive limit switches respond on approach of solid and liquid media.
Properties KG-201
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 110 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 0,55 V A
- Max. switching capacity : 36,3 V A
- Switching distance(mm) : 3...30
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,1 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED rot, eing.
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –25...+70 °C
Properties KG-200|KG-202
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 220 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 1,1 V A
- Max. switching capacity : 72,6 V A
- Switching distance(mm) : 3...20
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,5 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED gelb, intern
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –20...+60 °C
properties KG-211
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...30
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,1%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED rot, eing.
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –25...+70°C
Properties KG-210|KG-212
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...25
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,5%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED gelb, intern
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –20...+60°C
TK-301 PTFE
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 16
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 120 °C
- Operating pressure : max. 3 bar
- media density : 0,79 g/cm³
- Resolution (depending on type) : 7,5 mm |10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
ES-21
Electronic safety switching device with 1 safety function
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
Ex-BK
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –20...+120 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
- Dimensions : 80 mm x 75 mm x 57 mm
Material
- Housing : Aluminium
- Mounting clip : V2A
- Rivet : V2A
- Screw connection : M 20 x 1.5, V2A
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 24...250 V AC/DC
- Switching current : 20 mA...6 A AC/DC
- Switching capacity(min.) : max. 500 VA, 60 W
- Switching capacity(max.) : min. 2 VA/W
T-20x.F 230V
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Polyester
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : max. 80°C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
QFS-1X
Float switch with reed switch (mercury-free)
Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.
Properties
- Protection class EN60529 : IP 68
- Cable entry : PVC , PTFE
- Conductor cross-section : 3 x 0,75 mm², PUR 3x0,5mm²
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC (QFS-11 nur NO oder NC)
- Switching voltage : 4...250 V AC/DC
- Switching current : 1 mA ...1 A
- Switching capacity : max. 1A, 60 VA/60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. + 20° / – 20°
Float
- Material Float : PE (Polyethylen)
- ltdata. :
- ltdata. :
- ltdata. :
Operating temperature
- TPK(V), AEM : max. + 60 °C
- PUR : max. + 70 °C
- Silicone,Tefloncable with PE float : max. + 80 °C
Operating pressure
- Cylinder : max. 1 bar
- Sphere : max. 2 bar
QFSK-2X
Stainless steel float switch combination
Float switch combinations QFSK for level monitoring & level control with maximum and minimum contact sensor.
Properties
- Protection class EN60529 : IP 68
- Material Float : VA 1.4571
- Material hose : Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
- rod length : max. 5 m
- Number of floats : bis 5
- Operating temperature : max. + 150 °C
- media density : ρ ≥ 0,8g/cm³
- Switching system : Reed-Schalter
- Contact : Wechsler, NO, NC
- Switching voltage : 4...250 V AC/DC
- Switching current : 1 mA ...1 A
- Switching capacity : max. 1A, 60 VA/60 W
- Switching hysteresis : ca. 100 mm
- Switching angle : ca. + 20° / – 20°
- Ex-protection : optional; IBExU10ATEX 1089
- Operating pressure WFSK-25 : max. 15 bar
- Operating pressure QFSK-26 : max. 6 bar
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!