with general approval for constructions and EC-Type-Examination Certificate for Ex-zone 1(Cat. 2)
Properties
Protection class EN60529
:
IP 68
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
Resistance value of line monitoring
:
22 kΩ / 100 kΩ
cable length
:
auf Wunsch
Material
Cable
:
TPK (PVC Basis)
Sensor rods
:
Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
cable material
:
FEP (Teflon) | EX (PVC blau)
QFS-2X
Stainless Steel Float Switch
QFS-20 & QFS-21 float switches have stainless steel floats and one or two reed contacts.
Properties
Protection class EN60529
:
IP68
Material Float
:
VA 1.4571
Material hose
:
Edelstahlwellschlauch (1.4404) mit Edelstahldrahtumflechtung (1.4301)
Operating temperature
:
max. + 150 °C
media density
:
ρ ≥ 0,8g/cm³
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Operating pressure (QFS-20)
:
max. 15 bar
Operating pressure (QFS-21)
:
max. 6 bar
T20x.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Polyester
Box
:
Aluminium
Box
:
Polyethylen
Box
:
Kabel
Box
:
Stecker
Properties
Protection class EN60529
:
IP 65
connection thread
:
G 1", G 1¼", G 1½", G2", G3”
Union nut
:
G 2¾", S 100x8
Guide tube length
:
max. 6 m
Operating temperature
:
atmosphärisch; PP max. 90°C
Operating pressure
:
Max. 20 bar
media density
:
ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ltdata.
:
EE-2XF
Conductive electrodes as overfill protection for Ex-Zone 0 (Cat. 1)
Conductive electrodes EE-2XF for monitoring conductive liquids within the Ex area Zone 0 (Cat. 1) for water-polluting and flammable liquids.
Properties
connection
:
Edelstahl (1.4571)
Protection class
:
IP 65
Ex-protection
:
TÜV 02 ATEX 1796 X
Ex protection type
:
II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6
connection thread
:
G1", G1¼", G1½”
Coating length
:
voll=ganzer Stab (10 mm am Stabende sind blank) teil =ca. 250 mm von oben
Rod diameter
:
4 oder 6 mm
rod length
:
max. 6 m
Operating pressure media side
:
max. 40 bar
Maximum permissible electrical connection values
:
Stromkreis in Zündschutzart Eigensicherheit Ex ia IIC/IIB
Connection values
:
Ui 15V | Li 10 mA | Pi 100 mW
Internal inductances / capacitances
:
vernachlässigbar klein
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Operating temperature
Category 1 Class T6...T1
:
60 °C
Category 2 Class T6
:
Medien & Umgebung 80 °C
Category 2 Class T5
:
Medien & Umgebung 95°C
Category 2 Class T4
:
Medien 130°C, Umgebung 100°C
Category 2 Class T3...T1
:
Medien 150°C, Umgebung 100 °C