Ex-Electrode-single with integrated safety barrier
When using a threshold detection electrode with integrated safety barrier, exceeding or falling below a threshold in conductive fluids in Ex-Zone 0 (category 1) can be detected.
Properties
connection thread
:
G 1/2” Standard | G 3/4” | G1”
Cable
:
TPK (Standard) | SIL (Silikon) | FEP (Teflon)
rod length
:
max. 6.000 mm
Operating pressure
:
max. 40 bar
Material
electrode body
:
Edelstahl 1.4571
Process connection
:
Edelstahl 1.4571
Coating
:
PTFE
electrode rod
:
Edelstahl 1.4571
on request
:
Hastelloy C | Tantal
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
EE-2XF
Conductive electrodes as overfill protection for Ex-Zone 0 (Cat. 1)
Conductive electrodes EE-2XF for monitoring conductive liquids within the Ex area Zone 0 (Cat. 1) for water-polluting and flammable liquids.
Properties
connection
:
Edelstahl (1.4571)
Protection class
:
IP 65
Ex-protection
:
TÜV 02 ATEX 1796 X
Ex protection type
:
II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6
connection thread
:
G1", G1¼", G1½”
Coating length
:
voll=ganzer Stab (10 mm am Stabende sind blank) teil =ca. 250 mm von oben
Rod diameter
:
4 oder 6 mm
rod length
:
max. 6 m
Operating pressure media side
:
max. 40 bar
Maximum permissible electrical connection values
:
Stromkreis in Zündschutzart Eigensicherheit Ex ia IIC/IIB
Connection values
:
Ui 15V | Li 10 mA | Pi 100 mW
Internal inductances / capacitances
:
vernachlässigbar klein
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Operating temperature
Category 1 Class T6...T1
:
60 °C
Category 2 Class T6
:
Medien & Umgebung 80 °C
Category 2 Class T5
:
Medien & Umgebung 95°C
Category 2 Class T4
:
Medien 130°C, Umgebung 100°C
Category 2 Class T3...T1
:
Medien 150°C, Umgebung 100 °C
The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
Housing
:
Kunststoff
Protection class
:
IP00
Ambient temperature
:
-20…+60°C
Supply voltage
:
24V DC +20% / -10%
Our application engineers advise you