The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
TK-303
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class
:
IP 65
Float type
:
03, 04, 09
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar (Kugel) max. 15 bar (Zylinder)
Resolution
:
7,5 mm | 10 mm
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 03
:
0,75 g/cm³
Type 04
:
0,65 g/cm³
Type 09
:
0,76 g/cm³
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
Weight
:
ca. 150g
ltdata.
:
Power supply
nominal voltage
:
siehe Typenschlüssel
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Switching delay
:
siehe Typenschlüssel
Sensitivity range
:
siehe Typenschlüssel
Output
Contacts
:
potentialfreie Wechselkontakte
Switching voltage(min)
:
5 V
Switching voltage (max)
:
250 V AC / 150 V DC
Overvoltage category
:
EN 61010-1 Kategorie III
Switching current
Switching current
:
min. 5 mA
Switching current
:
max. cos φ =1 5 A
Switching current
:
max. cos φ = 0,7 3 A/AC
Switching current
:
max. cos φ = 1
KS-17
digital climate transmitter
The digital climate sensor measures temperature and relative humidity in a combined sensor element.
Technical specifications
Housing
:
Plastik
Measured variable
:
Temperatur und relative Feuchte kapazitiv (alle Geräte)
Measurable temperature
:
-40…+120 °C
Measuring range humidity
:
0…100 % rH
Sensor technology
:
Halbleiter
Power supply
:
2,4…5,5 V
Output
:
digitales Protokoll
features
:
Gehäuse für Oberflächenmontage
QFS-5x | QFS-6x
Teflon float switch for all kinds of liquids up to 150°C
The float of the QFS-50 and QFS-60 float switches is made of Teflon. Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.