Cart
product added to request
BK-380 configure
EFV2 24V configure
T-200.L Ex configure
ZMF-201e-IR configure
BK-380
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
T204-0.F
Immersible Magnetic Probe for Ex Zone 0 (Cat. 1)
The T20... magnetic immersion probes are used to detect fill level limits in containers for liquid media, where an explosive atmosphere of Zone 0 (Cat. 1) exists in the gas space above the liquid and an Ex-Zone 1 (Cat. 2) exists outside the container in the area of the junction box.
Properties
- connection : Kabel PUR blau
- Protection class : IP 68 Dose
- number of floats : max. 4x
- Operating temperature : max. 135 °C
- F-Contact : 1 / 12 kΩ
- Number of additional contacts : max. 3x Wechsler | 5x Schließer | 3x Öffner
- Switching current : 1 A, 2 A (nur mit Schirmung)
- Switching voltage : 230 V AC
Float
- Stainless steel ball 61 mm Ø : max. 20 bar | 0,65 g/cm³
- min. contact gap type 04 : 85 mm
Switching contacts and switching capacity
- Changeover contact : max. 3x | 60W/VA
- normally open : max. 5x | 100 W / VA
- Normally closed contact : max. 3x | 60 W/VA
EFV2 24V
adaptive conductive electrodes with and without 24 V direct connection
The conductive electrode EFV2 is approved by the "DIBt" as an overfill prevention device for liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
- Cable : Kabel (TPK)
- Plug : Stecker (ST)
Properties
- Protection class : IP 65
- connection thread : G2"
- Union nut : G2¾", S 100x8
- Material Screw connection : PE, PVC, PPH, PVDF
- Material Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal, Kohlestifte
- Operating temperature : PE, PVC: atmosphärisch PPH : 90 °C, PVDF: 100 °C
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ je nach Ausführung
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PVDF : 100 °C
Technical specifications electronic part
- Operating temperature : –20...+85 °C
- Storage temperature : –30...+85 °C
- nominal voltage : 24...30 V DC
- Power consumption : max. 2 W
- Switching voltage : max. 230 V AC / V DC min. 5 V DC (CMOS-Relais)
- Switching current : max. 0,12 A AC / A DC min. <1 mA
- Switching capacity : max. 25 VA / W
- Sensitivity : 3k … 100 kΩ
SG2420
Supply unit SG2420 for flow sensor
The DSM-2420 sensor can only be operated in hazardous areas with the associated SG2420 power supply unit or appropriately designed, approved Zener barriers.
Properties
- Housing : Kunststoff
- Protection class : IP00
- Ambient temperature : -20…+60°C
- Supply voltage : 24V DC +20% / -10%
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
- Box : Ex-Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung, PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- media density : mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- Leakage detection : ca. 12 kΩ
- Switching time : ca. 20 ms
ZMF-201e-IR
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-20X series includes sensors & transmitters for measuring gas concentrations of various gases such as CO2, methane, propane and SF-6.
This makes the sensors suitable for many applications. The ZMF-20X gas sensors are designed to be extremely rugged & suitable for use
in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Certification : SIL2, ATEX
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
Options
- Other cable lengths on request :
- ATEX certification (optional) :
Measuring ranges
- in ppm : in vol%
- 0…44.000ppm : 0…4,4 % vol (100 % LEL)
- 0…50.000ppm : 0…5 % vol
- 0…1.000.000ppm : 0…100 % vol
ZDT-H
Differential pressure transmitter for high pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (oponal)
- Overpressure : 1,2* (1,5*) x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA, 2-Leiter 4...20 mA, 3-Leiter
- Pressure range : 5…1.000 bar
Operating conditions
- Operating voltage : 14...28 VDC ± 10 %
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : G1/4" (andere auf Anfrage)
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!