ZMF-202e-IR configure
EF2...5 configure
EFV2 20…230V configure
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff
- LCD display : optional
- Signal output : 0…10 V | 4…20 mA
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
Operating conditions
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
ZDS-Serie
Precision pressure switch in robust design and first-class technical features.
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Properties ZDS-N
- Pressure range (stepped) : 0...500 mbar
- supply : 12 - 24 V DC
- Output : Relais 230 V/1A
- overload : 2 x Messbereich
- Med. connection : Schlauch
- electrical connection : Schraubklemme
- feature : Tasten, LCD-Anz.
Properties ZDS-H
- Pressure range (stepped) : 0...2.000 bar
- supply : 24 V DC
- Output : Relais 60 V AC/1A
- overload : 1,5 x Messbereich
- Med. connection : G 1/4 Zoll
- electrical connection : Schraubklemme
- feature : Tasten, LCD-Anz.
TPS-Serie
Sensors for determining the dew point in a wide range of applications
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Operating conditions
- Temperature: : -40...80°C
- rel. Humidity : 0 - 100% rH
Measuring range
- measuring range (dew point) : -50...+80°C
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V oder 4...20mA
ZMF-202e-IR
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-202e-IR is a propane sensor for measuring propane concentration in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Certification : SIL2, ATEX
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
Measuring ranges
- in ppm : in vol%
- 0...17.000ppm : 0…1,7 vol% (100 % LEL)
- 0...21.000ppm : 0…2,1 vol%
Options
- Other cable lengths on request :
- ATEX certification (optional) :
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
DS-CAN-01
CANopen pressure transmitter with CAN bus signal output
Versatile, media-compatible pressure transmitter with CAN bus interface.
technical properties
- Pressure type : Relativdruck gegen Umgebungsdruck bzw. gegen interne Atmosphäre
- measuring resolution : 10 Bit
- Measuring accuracy : Klasse 0,5 bei RT
- Total error : < 1,5 % v.E bei -10 °C … +80 °C.
- measuring grid : ab 5 ms
- CAN protocol : CANopen 2.0 A
- Physical Layer : nach DIN 11898
ambient conditions
- Operating temperature range : -40 °C … +80 °C
- Storage temperature range : -40 °C … +120 °C
- Shock resistance : 30 g, Dauer
- Vibration resistance : 10 g bei 20-1000 Hz
- EMC/ESD : EN 50082-1 und EN 50082-2
- Duration : 14 ms bei RT
Pressure measuring ranges
- kPa : bar
- 0...500 : 0…5
- 0...1.000 : 0…10
- 0...2.000 : 0…20
- 0...5.000 : 0…50
- 0...10.000 : 0…100
- 0...35.000 : 0…350
- 0...50.000 : 0…500
- 0...70.000 : 0…700
- 0...200.000 : 0…2.000
- 0...400.000 : 0…4.000
- Standard pressure range : in kPa
- Non-standard ranges : auf Anfrage erhältlich
EFV2 20…230V
Conductive electrodes with 24...230 V direct connection
The overfill protection EFV2 (24...230 V AC/DC) is approved by the "DIBt" as overfill protection for liquids hazardous to water.
Properties
- connection : Polyesterdose (PO)
- Protection class : IP 65
- connection thread : G2"
- Union nut : G2¾" | S 100x8
- Material Screw connection : PE, PVC, PPH, PVDF
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Kohlestifte
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 100 kΩ
- Adjustable sensitivity range : 2..100 kΩ
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PVDF : 100 °C
Power supply
- nominal voltage : 24...230 V AC/DC
- Power consumption : ≤ 2 W
Output
- potential-free changeover contacts : 2
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs- LED grün Funktions-LED rot
- Switching delay : ca. 0,5 s
KS-210 KS-220
Compact sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Properties KS-210
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
Properties KS-220
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (Humidity) : 0…10% rH
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
Our application engineers advise you personally, comprehensively and professionally!