Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
T207
Magnetic immersion probes made of PPH
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
connection
:
Polyesterdose | Aluminiumdose
Protection class EN60529
:
IP 65 Anschlussdose
Connector plug
:
3- und 6-fach
connection thread
:
G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
connection cable
:
LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
Sliding tube length
:
max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
Operating pressure
:
max. 20 bar
Viscosity
:
< 100 cp
Protection class EN60529
:
IP 68 Führungsrohr
Switching voltage
:
max. 250 V
Switching hysteresis
:
ca. 2...5 mm
Holding range
:
ca. 12 mm
Contact function
:
monostabil | bistabil
Operating temperature
ltdata.
:
max. +60...+150 °C
ltdata.
:
min. –20... –10 °C
ltdata.
:
höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
Changeover contact
:
60 W/VA
normally open
:
100 W/VA
Normally closed contact
:
60 W/VA
Switching current
Changeover contact
:
max. 1 A
NO/NC contact
:
max. 2 A
Contacts
Changeover contact
:
8
normally open
:
10
Normally closed contact
:
7
TK-312
Evaluation unit with 0/4... 20 mA current output
The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA, 2W
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0-4...10 kW
Output
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Current output
:
0/4... 20 mA bezogen auf die Masse des Eingangs
Voltage output
:
0/2... 10 V
Mounting
:
Tragschiene nach EN 50022
Weight
:
175 g
TK-300
Level transducer
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties TK-300
connection
:
Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
10 (14)
connection cable
:
1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating pressure
:
max. 6 bar
Resolution
:
10 mm, 15 mm oder 1%, 2%, 5% je nach Auflösung
CE marking
:
siehe Konformitätserklärung
Operating temperature
PV
:
max. 60°C
PE
:
max 80 °C
PP
:
max. 90°C
MaterialDensity
Type 10
:
0,72 g/cm³
Type 14
:
0,72 g/cm³
Type 18
:
0,82 g/cm³
TK-307
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Connection housing
:
Aluminium H 30 mm x B 50 mm x T 45 mm
Connection socket
:
Polyester H 55 mm x B 80 mm x T 45 mm
Protection class socket / plug
:
IP 65
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Resolution depending on type
:
7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
Mounting
:
2 Schlauchschellen
Accessories
:
R/I-Wandler TK-101
ZT-H
High pressure sensor for liquid and gaseous media
Versatile use in industrial applications for measuring ranges up to 4,000bar
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6