The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-410
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Protection class Housing
:
IP66
Protection class plug
:
IP67
Weight
:
96g
Properties TPS-420
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (dew point)
:
-50…+80 °C
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
ZT-N
Customisable low pressure sensor for precise measurement of the smallest pressures
Reliable low pressure sensor in a robust and compact design
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
KS-CAN-03
CANopen Climate Transmitter
Climate transmitter KS-CAN-03 for temperature and humidity measurement, according to CAN bus specifications with a digital climate probe
Properties
Housing
:
Aluminium, eloxiert
Measuring element humidity
:
kapazitiv, betauungsfest
Measuring element temperature
:
Halbleiter
measuring resolution
:
12 Bit
measuring grid
:
ab 5 ms
ElectricalConnection
CAN protocol
:
CANopen 2.0 A, nach ciA DS 404
Physical Layer
:
nach DIN 11898
Option
:
Bereistellung des EDS-Files
tdata.
Operating temperature
:
-40...+80 °C
Storage temperature
:
-40°C...+120°C
Minimum air velocity across the sensor required for measurement
:
1,5 m/s
VS-D250
Transmitter for ViscoScope viscosity sensors
Maximum flexibility for an optimal choice of measuring instrument: The VS-D250 transmitter is compatible with all ViscoScope® sensors of the types VA-100 and VA-300.
Properties
Output card socket
:
2
External input
:
0/4…20 mA | 0/2…10 V DC
Power supply
:
24V DC, 12 W
Dimensions
:
142 x 106 x 73 mm (L x B x H)
Front
:
RS232, MODBUS RTU (Standard)
Display and Operation
Lines
:
4
Pages
:
2
Character set
:
alphanumerisch
Buttons
:
3 (front)
Alarms
system function
:
sensor diagnosis
:
Coil Temperature
:
2 configurable LEDs
:
optional outputs
0/4…20mA | 0/2…10V DC (active)
:
RS232 | RS485
:
2 SPDT-Relays: RS232 | RS485
:
Filter
Moving average (200 measured values)
:
ER-214
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Weight
:
ca. 150 g
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Output
Contacts
:
1 potentialfreie Wechselkontakte pro Kanal
Switching voltage
:
min. 5 V | max. 250 V AC | max. 150 V DC
Switching current
:
min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
Switching capacity
:
min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
Working / Idle current
:
umschaltbar
overvoltage category
:
EN 61010-1 Kategorie III
Our application engineers advise you