Cart
product added to request
XR-4x2 configure
EF2...5 configure
T-200.L 230V configure
ZT-V configure
FDL400
Flow Data Logger
The FDL400 "Flow Data Logger 400" measuring device is suitable for measuring the flow of water and wastewater in fully or partially filled sewers or pipes of various geometries.
Properties
- Housing : Aluminium
- Protection class : IP30
- Dimensions : 197 x 153 x 37,5mm (B x H x T)
- Temperature range : 0 – 50°C
- Supply voltage : 24V DC +/-20%
- Power consumption : 120mA – 220mA
- Reverse polarity protection : ✓
- Display : 4x20
Outputs
- analog 0(4)–20mA : 3x
- digital : 4x
- fixed for alarm : 1x
- free configurable : 3x
display of measured value
- Flow velocity :
- Filling level :
- flow :
- flow rate :
T205 VA
Stainless steel magnetic immersion probes
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 65
- Number of floats : max. 2x Typ 08
- connection cable : Silikon Litze
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar (Zylinder)
- Number of contacts : max. 2 x Schließer/ Öffner wahlweise durch 180°-Drehung des Schwimmers bei 2 Schwimmern
- Switching current : 1 A
- Switching voltage : 250 V AC
- Switching capacity : 50 W/VA
- Sliding tube length : max. 1000 mm
- media density : Typ 08: 0,78 g/cm³
- float : Zylinder Edelstahl 1.4571 27 mm Ø
- min. contact distance with several floats : 50 mm
XR-4x2
Electrode relay with ATEX and WHG approval
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
T-200.L 230V
Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
- Box : Polyesterdose (PO)
Properties
- Protection class : IP 65
- Cable entry : PVDF-Verschraubung , PVC-Dichtung
- Material Float : PE
- Material leakage probe base : PE
- Cable : TPK (PVC Basis)
- Operating temperature : max. 60 °C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : ≤ 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
- CE marking : siehe Konformitätserklärung
ZT-V
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Connection
- Signal output : 0...10 V, 3-Leiter | 0,5...4,5, ratiometrisch | 4...20 mA, 2-Leiter
- Electrical connection : DIN EN 175301-803 A | DIN EN 175301-803 C | Binder M12x1 (Serie 713)
- Process connection : G 1/4" ISO 1179-2 (Male Form E) | 1/4" NPT | 7/16" 20 UNF Male
- measuring range (bar) : 0…0,6 | 0…600
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40°C...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
Our application engineers advise you personally, comprehensively and professionally!