The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
Operating temperature
:
-20...+60 °C
Storage temperature
:
-40...+80 °C
Ex-protection
:
siehe Zertifikat
CE marking
:
siehe Konformitätserklärung
Input
Resistance range in three-wire circuit
:
4...10 kΩ
Measuring current
:
0,8 mA @ RE = 4 kΩ
Measuring current
:
0,33 mA bei RE = 10 kΩ
Measuring voltage
:
3,3 V
Supply/Output
2-wire
:
4...20 mA
Voltage(Um)
:
11...28 V DC
Burden / load
:
0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
Output signal in case of error
:
max. 24 mA
Fault influences
Max. Total error
:
± 1 %
Temperature influence
:
-0,015 % / °C
Supply voltage influence
:
0,025 % / V
Setting range
Full deflection
:
60...105 %
Zero point adjustment
:
0...25 %
TK-309
Stainless steel level sensor
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
07
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 130 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm | 1% | 2% | 5%
Accessories
:
R/I-Wandler TK-101
TK-303
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
connection
:
Dose
Protection class
:
IP 65
Float type
:
03, 04, 09
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar (Kugel) max. 15 bar (Zylinder)
Resolution
:
7,5 mm | 10 mm
Accessories
:
R/I-Wandler TK-101
MaterialDensity
Type 03
:
0,75 g/cm³
Type 04
:
0,65 g/cm³
Type 09
:
0,76 g/cm³
ER-104
1-channel electrode relay
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
Storage temperature
:
–30...+80 °C
Weight
:
ca. 150g
ltdata.
:
Power supply
nominal voltage
:
siehe Typenschlüssel
AC nominal frequency
:
48...62 Hz
Power consumption
:
max. 1 W / VA
Input
Open circuit voltage
:
≤ 10 V AC
Short-circuit current
:
≤ 5 mA
Switching delay
:
siehe Typenschlüssel
Sensitivity range
:
siehe Typenschlüssel
Output
Contacts
:
potentialfreie Wechselkontakte
Switching voltage(min)
:
5 V
Switching voltage (max)
:
250 V AC / 150 V DC
Overvoltage category
:
EN 61010-1 Kategorie III
Switching current
Switching current
:
min. 5 mA
Switching current
:
max. cos φ =1 5 A
Switching current
:
max. cos φ = 0,7 3 A/AC
Switching current
:
max. cos φ = 1
TK-301 PTFE
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
16
connection cable
:
1000 mm Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 120 °C
Operating pressure
:
max. 3 bar
media density
:
0,79 g/cm³
Resolution (depending on type)
:
7,5 mm |10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
BI
Bistable Switch
Properties
Protection class
:
IP 65
Switching current
:
max. 1 A
Switching voltage
:
max. 24 V
Switching capacity
:
max. 20 W/VA
Material
Housing
:
Messingrohr Ø 10 x 1
Cable
:
TPK (PVC basis) | SIL (Silikon)
Operating temperature
TPK
:
–15 ° ... + 60 °C
SIL
:
–15 ° ... +130 °C
EF 3…5 24 V
Conductive electrodes with 24 V DC direct connection
The conductive electrodes EF3...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
connection
:
integrierter Anschlusskopf
Protection class
:
IP 65
connection thread
:
G 1¼"
Material Screw connection
:
PPH
Material electrode rods
:
Edelstahl (1.4571), Hastelloy C, Titan, Tantal
material coating
:
PTFE
Coating length
:
voll = ganzer Stab (10 mm am Stabende sind blank) teil = ca. 250 mm von oben
Rod diameter
:
4 mm, 6 mm
rod length
:
max. 6 m
Operating temperature
:
85 °C
Operating pressure
:
atmosphärisch
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Properties electronic part
Operating temperature
:
–20...+85 °C
Storage temperature
:
–30...+85 °C
nominal voltage
:
24 V DC ± 15%
Power consumption
:
max. 2 W (Klemme A1, A2)
Switching voltage
:
max. 250 V AC, 150 V DC min. 5 V DC (Relais mit Kombi-Goldkontakten)
Switching current
:
max. 3 A AC, 3 A DC min. 1 mA
Switching capacity
:
max. 750 VA, 150 W
Sensitivity
:
3k ... 100 kΩ in vier Stufen (3 k, 10 k, 30 k, 100 kΩ) wählbar
TK-312
Evaluation unit with 0/4... 20 mA current output
The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA, 2W
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0-4...10 kW
Output
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Current output
:
0/4... 20 mA bezogen auf die Masse des Eingangs
Voltage output
:
0/2... 10 V
Mounting
:
Tragschiene nach EN 50022
Weight
:
175 g
Our application engineers advise you