CO2 sensor for measuring room air quality with visual and acoustic warning signal output
Multifunctional CO2 sensor with LED display and acoustic alarm, equipped with switching functions for both industrial and private applications (0...3.000ppm)
Product features
Product type
:
CO2-Sensor zur Bewertung und Überwachung der Luftgüte
Measuring principle
:
Basierend auf optischem Messprinzip (NDIR)
Measuring range
:
Lieferbar in unterschiedlichen Messbereichen (Standard 0…3.000ppm)
Display
:
Darstellung der CO2-Konzentration mittels Bargraphanzeige (Luftgüteampel)
Accuracy
:
+-3% vom Messbereich (30 ppm bei 3.000 ppm)
Relay output:
:
Potentialfrei
Response time
:
ca. 20 s
Operating voltage
:
24 V DC, 150 mA
ViscoScope® VA-100
Inline Viscometer
Maintenance-free inline viscosity sensor for precise and reliable real-time measurement of viscosity directly in the process.
Properties
Material
:
1.4571 / 1.4404 (316Ti / 316L)
Protection class
:
IP65
Process temperature
:
-10°C … +130°C | (integriertes Pt100 im Messfühler)
max. process pressure
:
Vakuum ... 64 bar
Process connections
:
NPT | M48 | Varivent® | Tri-Clamp
Cable length sensor - transmitter
:
Max. 1.000 Meter
max. flow velocity
:
5 m / sec
Ex approval
:
II 1/2G Ex ia IIC T6...T3 Ga/Gb | (optional)
Sensor types
Sphere
:
VA-100B
Cylinder
:
VA-100C
Repeatability
VA-100B
:
± 0,5% | ± 1 Digit
VA-100C
:
± 0,3% | ±1 Digit
Measuring ranges
VA-100B
:
0,1 - 2.500 mPa·s x g/cm³
VA-100C
:
10 - 25.000 mPa·s x g/cm³
Probe dimensions
VA-100B
:
Ø 32 x 145 mm
VA-100C
:
Ø 32 x 120 mm
installation positions
Reservoir
:
tanks
:
Pipe
:
flow cell
:
Installation is position-independent
:
TK-312
Evaluation unit with 0/4... 20 mA current output
The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA, 2W
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0-4...10 kW
Output
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Current output
:
0/4... 20 mA bezogen auf die Masse des Eingangs
Voltage output
:
0/2... 10 V
Mounting
:
Tragschiene nach EN 50022
Weight
:
175 g
Our application engineers advise you
personally, comprehensively and professionally!