Cart
product added to request
product added to request
T203 configure
BK-390 configure
T200.F-24V configure
TK-313 configure
T203
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
tdata.
- connection : Polyesterdose | Aluminiumdose
- Protection class : IP 65 Dose
- Guide tube : Edelstahl 1.4571, Ø 15 mm
- Guide Tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- F-Contact : 1/12 kΩ
- Switching current : 1A, 2A ( nur mit Schirmung)
Float types
- float type 05 : Dichte: 0,81 g/cm³ | 110 mm Abstand
- float type 06 : Dichte: 0,67 g/cm³ | 135 mm Abstand
Number of contacts
- Changeover contact : 5x
- normally open : 6x
- Normally closed contact : 4x
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
BK-390
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
T200.F-24V
Overfill protection with 24V direct connection
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Polyester junction box : PO/ET-520
- Polyethylene connection head : PE/ET-521
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : max. 80 °C
- Operating pressure : atmosphärisch
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Power supply
- nominal voltage : 24 V DC (24…300V DC)
- Power consumption : ≤ 1 W
Output
- Output contact : 1 potentialfreier Wechselkontakt
- Switching voltage : max. 250 V AC / 30 V DC
- Switching current : max. 3 A AC / 3 A DC
- Switching capacity : max. 750 VA / 90 W
Optocoupler
- Switching voltage : max. 30 V
- Switching current : max. 100 mA
- displays : Betriebs-LED grün, Funktions-LED rot
- Switching delay : ca. 0,5 s Anzug/Abfall
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- power : 0/4...20 mA
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0–4...10 kΩ
Output
- Output contacts : 2 Wechselkontakte
- Switching voltage : max. 250 V AC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Mounting : Tragschiene nach EN 50022
- Current output : 4...20 mA bezogen auf die Masse des Eingangs
- Display (%) : 2-stellig, 7-Segment
- Weight : 175 g
- ltdata. :
cIO CANopen Module
Compact I/O modules for DIN rail mounting
product series of compact CANopen I/O modules with various electrical connections
Properties
- Housing : Kunststoffgehäuse*
- Dimensions (LxBxH) : 18 x 90 x 62 mm
- Internal circuits : Ausgangsschutzschaltungen gegen Überspannung und elektrostasche Entladung
- Fieldbus and I/O level : getrennt durch galvanische Trennung
- ltdata.*zumAufrastenaufDIN-Trageschienen :
ElectricalConnection
- Operating voltage : 11...32V DC (typ. 24V DC)
- Operating temperature : 0...+55 °C
- Operating temperature : optional -40...+70 °C
- Conductor cross-section : 0,08...1,5 mm² (AWG28...AWG14)
CAN bus properties
- baud rate (max.) : 1 MBit
- ciA Standards : Ds301 Version 4.2 & DS401 Version 3.0
- ISO standards : ISO11898 (+ Transceiver TJA1050)
- PDO : siehe Dokumente
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!