Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
Box
:
Ex-Polyester
Box
:
Ex-Aluminium
Properties
Protection class EN60529
:
IP 65
connection thread
:
G2"
Union nut
:
G 2¾"
Guide tube length
:
max. 6 m
Operating temperature
:
-20…+60 °C
Operating pressure
:
max. 6 bar je nach Ausführung
media density
:
ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
Switching hysteresis
:
2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
overfill alarm
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
Ex-protection
:
siehe Baumusterprüfbescheinigung
CE marking
:
siehe Konformitätserklärung
EP
Plate Electrode as Leak Detector (conductive)
with general approval for constructions and EC-Type-Examination Certificate for Ex-zone 1(Cat. 2)
Properties
Protection class EN60529
:
IP 68
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
Resistance value of line monitoring
:
22 kΩ / 100 kΩ
cable length
:
auf Wunsch
Material
Cable
:
TPK (PVC Basis)
Sensor rods
:
Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
cable material
:
FEP (Teflon) | EX (PVC blau)
TK-309-0
Stainless steel level sensor for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class Socket
:
IP65
Float type
:
Typ 07
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. 135 °C
Operating pressure
:
max. 20 bar
media density
:
Typ 07: 0,54 g/cm³
Resolution
:
7,5 mm | 10mm |15 mm | 20 mm
Accessories
:
R/I-Wandler TK-101
KST-20 VENTO CO2
KST-20 Vento with air quality monitoring function
Automatic, controlled ventilation and dehumidification of rooms with the aH-Controlled technology*
Properties
measuring range (Humidity)
:
0…100 % rF,
Measuring accuracy (humidity)
:
±2 %
measuring range (Temperature)
:
-40…+80 °C
Measuring accuracy (temperature)
:
±0,2 °C
Signal output
:
I2C
measuring range (CO2)
:
0…5.000 ppm
Adjustable limits
:
1.000…1.500 ppm
Power supply
:
230 V AC
Protection class
:
IP 65
Dimensions (LxBxH)
:
160 x 90 x 50 mm
Housing
:
hochwertiges ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
Measuring range
measuring range (Humidity)
:
0...100 % rF
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80 °C
Measuring accuracy (temperature)
:
± 0,2 °C
measuring range (CO2)
:
0…5.000 ppm
Adjustable limits
:
1.000...1.500 ppm
Our application engineers advise you