Inside the float, one or two reed contacts with a movable permanent magnet are inserted as a switching element.
Properties
Protection class EN60529
:
IP 68
Cable entry
:
PVC , PTFE
Conductor cross-section
:
3 x 0,75 mm², PUR 3x0,5mm²
Switching system
:
Reed-Schalter
Contact
:
Wechsler, NO, NC (QFS-11 nur NO oder NC)
Switching voltage
:
4...250 V AC/DC
Switching current
:
1 mA ...1 A
Switching capacity
:
max. 1A, 60 VA/60 W
Switching hysteresis
:
ca. 100 mm
Switching angle
:
ca. + 20° / – 20°
Float
Material Float
:
PE (Polyethylen)
ltdata.
:
ltdata.
:
ltdata.
:
Operating temperature
TPK(V), AEM
:
max. + 60 °C
PUR
:
max. + 70 °C
Silicone,Tefloncable with PE float
:
max. + 80 °C
Operating pressure
Cylinder
:
max. 1 bar
Sphere
:
max. 2 bar
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff
LCD display
:
optional
Signal output
:
0…10 V | 4…20 mA
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Operating conditions
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
T-200.L Ex
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
Box
:
Ex-Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung, PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
CSC-20 YUGO
Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
Power supply
:
230 V AC
measuring range (CO2)
:
0..10.000 ppm
Measuring accuracy CO2
:
± 50ppm +3 % vom Messwert
Operating conditions
:
0…50°C / 0…85 %rH
Storage conditions
:
-30…70°C / 0…85 %rH
Protection class
:
IP 31
EMV/ESD
:
EN 50082-1, EN 50082-2
Signal output
:
I²C
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
Operating voltage
:
12...32 V DC (max. 0,2 W)
Dimensions
:
Ø 22 x 59 (D x H), SW22
Housing
:
Edelstahl
Measuring range nominal pressure
:
-1…500 bar
Overpressure
:
2 x Nenndruck
Bursting pressure
:
4 x Nenndruck
Protection class
:
IP65
Output signal
:
ZILA-DIO
Operating conditions
Pressure type
:
Relativdruck
Temperature of the fluid
:
-40 …+125 °C
fluid temperature (optional)
:
-20 …+125 °C
Ambient temperature
:
-40 …+105 °C
electrical connection
Standard
:
Binder M12 x 1
TK-30X
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties
connection
:
Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
connection thread
:
G 3/8”, G 1/2”, G 1”, G 1 1/2”, G 2”, G 3”
connection cable
:
LiYY max. 80 °C | Silikon max. 130 °C
Sliding tube length
:
max. 6000 mm
Operating temperature
:
max. +60...+130 °C | min. –20...–10 °C je nach Ausführung
Operating pressure
:
max. 20 bar je nach Ausführung
media density
:
siehe Schwimmerdaten
Viscosity
:
< 100 cp
Switching hysteresis
:
ca. halbe Auflösung
Resolution
:
7,5 mm, 10 mm, 15 mm, 20 mm oder 1 %, 2 %, 5 % je nach Ausführung
Total resistance
:
ca. 5 kΩ
Measuring voltage
:
max. 24 V
Measuring current
:
max. 5 mA
Our application engineers advise you
personally, comprehensively and professionally!