Cart
product added to request
product added to request
product added to request
TK-101 configure
ZMF-203e-IR configure
TK-315 configure
T20x.F configure
TK-101 EX configure
Ex-BK configure
TK-101
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
ZMF-203e-IR
Robust sulphur hexafluoride SF6 sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-203e-IR is an SF6 sensor for measuring sulphur hexafluoride concentration in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Certification : SIL2, ATEX
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- pressure conditions : 800...1200 mbar
- screw thread : M46x15
Measuring ranges
- in ppm : in vol%
- 0...1.000ppm : 0...0,1 vol%
- 0...2.000ppm : 0...0,2 vol%
Options
- Other cable lengths on request :
- ATEX certification (optional) :
TK-315
Evaluation unit with 4 limit contacts (NO-contacts)
The TK-315 limit comparator can be used in conjunction with our TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output signal for level control/measurement.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA
- Dimensions housing type B : 22,5 x 114,5 x 99 mm
- Dimensions housing type C : 22,5 x 114,5 x 114 mm
Input
- power : 0/4...20 mA
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0–4...10 kΩ
Output
- Output contacts : 4 Schließerkontakte
- Switching voltage : max. 250 V AC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Mounting : Tragschiene nach EN 50022
- Current output : 4...20 mA bezogen auf die Masse des Eingangs
- Display (%) : 2-stellig, 7-Segment
- Weight : 175 g
T208
Immersible Magnetic Probe made of PVC, PE, PPH
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- connection : Polyesterdose | Aluminiumdose
- Protection class EN60529 : IP 65 Anschlussdose
- Connector plug : 3- und 6-fach
- connection thread : G 1/8" | G 3/8" | G 1/4" | G 1/2" | G 1" | G1 1/4" | G1 1/2" | G2" | G3"
- connection cable : LiYY max. 80 °C | PTFE-Litze, 0,24 mm² | Silikon max. 150 °C
- Sliding tube length : max. 1000 mm (Rohr Ø 8 mm) | 6000 mm
- Operating pressure : max. 20 bar
- Viscosity : < 100 cp
- Protection class EN60529 : IP 68 Führungsrohr
- Switching voltage : max. 250 V
- Switching hysteresis : ca. 2...5 mm
- Holding range : ca. 12 mm
- Contact function : monostabil | bistabil
Operating temperature
- ltdata. : max. +60...+150 °C
- ltdata. : min. –20... –10 °C
- ltdata. : höhere oder niedrigere Temperaturen auf Anfrage
Switching capacity
- Changeover contact : 60 W/VA
- normally open : 100 W/VA
- Normally closed contact : 60 W/VA
Switching current
- Changeover contact : max. 1 A
- NO/NC contact : max. 2 A
Contacts
- Changeover contact : 8
- normally open : 10
- Normally closed contact : 7
T206
Magnetic immersion probes made of PP or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Number of contacts : 1 x Schließer/Öffner durch 180°-Drehung des Schwimmers
- Switching current : 1 A
- Switching capacity : 50 W/VA
T206PP
- Float type : max. 2 x Typ 12 (13)
- max. 2x Type 12(13) : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : 60 °C
- Operating pressure : drucklos
- media density : Typ 12: 0,93 g/cm³ | Typ 13: 0,68 g/cm³
- min. contact distance with several floats : 50 mm
T206VA
- Protection class EN60529 : IP 65
- Float type : max. 2 x Typ 08
- connection cable : PTFE-Litze 0,24 mm²
- Sliding tube length : max. 1000 mm
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar
- media density : Typ 08: 0,78 g/cm³
- min. contact distance with several floats : 42 mm
T20x.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Polyester
- Box : Aluminium
- Box : Polyethylen
- Box : Kabel
- Box : Stecker
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating temperature : atmosphärisch; PP max. 90°C
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
ELH
Suspension electrode as leakage probe
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
TK-101 EX
Measuring transducer (R/I-transducer)
The measuring transducer Tk101 and Tk101Ex are built directly into the connection boxes of our Liquid Level Measuring Instruments of type TK-30.
Properties
- Operating temperature : -20...+60 °C
- Storage temperature : -40...+80 °C
- Ex-protection : siehe Zertifikat
- CE marking : siehe Konformitätserklärung
Input
- Resistance range in three-wire circuit : 4...10 kΩ
- Measuring current : 0,8 mA @ RE = 4 kΩ
- Measuring current : 0,33 mA bei RE = 10 kΩ
- Measuring voltage : 3,3 V
Supply/Output
- 2-wire : 4...20 mA
- Voltage(Um) : 11...28 V DC
- Burden / load : 0...800 Ω |RBürde max = [(Um - Um min) / 0,02] Ω
- Output signal in case of error : max. 24 mA
Fault influences
- Max. Total error : ± 1 %
- Temperature influence : -0,015 % / °C
- Supply voltage influence : 0,025 % / V
Setting range
- Full deflection : 60...105 %
- Zero point adjustment : 0...25 %
ZDS-N
Precision pressure switch for low pressure applications
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
technical properties
- Pressure range : 0...500mbar gestuft
- supply : 12 - 24 V DC
- Output : Relais 230 V/1A
- overload : 2 x Messbereich
- Med. connection : Schlauch
- electrical connection : Schraubklemme
- feature : Tasten, LCD-Anz.
CSC-20 YUGO
Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
- Power supply : 230 V AC
- measuring range (CO2) : 0..10.000 ppm
- Measuring accuracy CO2 : ± 50ppm +3 % vom Messwert
- Operating conditions : 0…50°C / 0…85 %rH
- Storage conditions : -30…70°C / 0…85 %rH
- Protection class : IP 31
- EMV/ESD : EN 50082-1, EN 50082-2
- Signal output : I²C
Ex-BK
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –20...+120 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
- Dimensions : 80 mm x 75 mm x 57 mm
Material
- Housing : Aluminium
- Mounting clip : V2A
- Rivet : V2A
- Screw connection : M 20 x 1.5, V2A
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 24...250 V AC/DC
- Switching current : 20 mA...6 A AC/DC
- Switching capacity(min.) : max. 500 VA, 60 W
- Switching capacity(max.) : min. 2 VA/W
ER-Serie
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- details : folgen
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!