Sensor for simultaneous measuring flow velocity and filling level
The DSM2420 sensor is a combined sensor for simultaneous measuring flow velocity and level in open or accessible closed channels of all types and shapes.
Properties
Dimensions
:
180 x 48 x 36,5 mm ( L x B x H )
Weight
:
ca. 1,5 kg
Protection class
:
IP68
Cable length (standard)
:
15 m
Bending radius
:
> 10 x D (Kabeldurchmesser 6,25mm) = > 62,5mm
Temperature range
:
0°C ... 50°C
Mounting shoe material
:
V2A 1,5mm
Certificates
EX / ATEX
:
IBExU 04 ATEX 1256
Measuring principle
Flow velocity: Ultrasonic Doppler
:
Filling level: Differential pressure
:
Flow velocity
Measuring range
:
0,01 - 4 m / s
Measuring accuracy
:
+/- 5 % vom Momentanwert im Kanal
Temperature drift
:
0,1% / °C ( Meßspanne )
Temperature drift
:
0,05% / °C ( Nullpunkt )
Output signal
:
4 - 20 mA
Filling level
Measuring ranges
:
0 –1 m ; 0 – 2 m ; 0 – 4 m
Measuring accuracy
:
< 0,2% v.E. Summe aus Nichtlinearität, Hysterese und Wiederholbarkeit
Temperature drift
:
0,005% / °C v.E. Meßspanne
Temperature drift
:
0,005% / °C v.E. Nullpunkt
Material
:
Al2O3 (96%) aktive Fläche
Output signal
:
4 – 20 mA
Zero point
:
norm 4 mA ( +/- 3 % )
NSP-X-E
Vibrating Limit Switch
The vibrating limit switch is a level limit switch for all kinds of fluids and is used in tanks, containers and pipelines.
Properties
Protection class EN60529
:
IP 65/IP 67
Operating pressure
:
≤ 40 bar
media density
:
ρ ≥ 0,7 g/cm³
Viscosity
:
max. 10000 mm²s
Rated current
:
< 15 mA
Protection class
:
III
Output
:
PNP
power
:
kurzschlussfest, überlastsicher
Display
:
LED (grün, rot)
Switching delay (cover)
:
ca. 0,5 s
Switching delay (release)
:
ca. 1 s
NSP-1-E
connection thread
:
G 1”
Operating temperature
:
–40...+150 °C
Storage temperature
:
–40...+85 °C
nominal voltage
:
10...55 V DC (verpolsicher)
Current output
:
≤ 350 mA
NSP-2-E
connection thread
:
G ½”
Operating temperature
:
–40...+100 °C
Storage temperature
:
–20...+70 °C
nominal voltage
:
10...35 V DC (verpolsicher)
Current output
:
≤ 250 mA
CSC-20 YUGO
Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
Power supply
:
230 V AC
measuring range (CO2)
:
0..10.000 ppm
Measuring accuracy CO2
:
± 50ppm +3 % vom Messwert
Operating conditions
:
0…50°C / 0…85 %rH
Storage conditions
:
-30…70°C / 0…85 %rH
Protection class
:
IP 31
EMV/ESD
:
EN 50082-1, EN 50082-2
Signal output
:
I²C
Our application engineers advise you
personally, comprehensively and professionally!