Evaluation unit with 4 limit contacts (NO-contacts)
The TK-315 limit comparator can be used in conjunction with our TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output signal for level control/measurement.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA
Dimensions housing type B
:
22,5 x 114,5 x 99 mm
Dimensions housing type C
:
22,5 x 114,5 x 114 mm
Input
power
:
0/4...20 mA
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0–4...10 kΩ
Output
Output contacts
:
4 Schließerkontakte
Switching voltage
:
max. 250 V AC
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Mounting
:
Tragschiene nach EN 50022
Current output
:
4...20 mA bezogen auf die Masse des Eingangs
Display (%)
:
2-stellig, 7-Segment
Weight
:
175 g
XR-6x0 | XR-6x1
Contact protection relay Measuring transducer
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
clamp
:
IP20
Housing
:
IP40
Technical Data
Operating temperature
:
-20...+60 °C
Storage temperature
:
-30...+80 °C
Output contacts
:
potentialfrei
Switching voltage
:
min. 5 V, max. 250 V AC / 150 V DC
Switching current
:
min. 5 mA, max. 5 A AC / 5 A DC
Switching capacity
:
min. 300 mW, max.100 VA / max. 50 W
Leakage probes with general building authority approval for hazardous areas
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaking water-polluting liquids. The T-200.L Ex may be used as leakage probes in hazardous areas, zone 1 (category 2).
Connection
Box
:
Ex-Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung, PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
media density
:
mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Resistance value
Operational readiness
:
ca. 1 kΩ
Leakage detection
:
ca. 12 kΩ
Switching time
:
ca. 20 ms
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
Operating voltage
:
12...32 V DC (max. 0,2 W)
Dimensions
:
Ø 22 x 59 (D x H), SW22
Housing
:
Edelstahl
ltdata.MessbereichNenndruck
:
-1…500 bar
Overpressure
:
2 x Nenndruck
Bursting pressure
:
4 x Nenndruck
Protection class
:
IP65
Output signal
:
ZILA-DIO
Operating conditions
Pressure type
:
Relativdruck
Temperature of the fluid
:
-40 …+125 °C
ltdata.Medientemperatur(optional)
:
-20 …+125 °C
Ambient temperature
:
-40 …+105 °C
electrical connection
ltdata.Standard
:
Binder M12 x 1
Our application engineers advise you
personally, comprehensively and professionally!