Cart
product added to request
T-200.F Ex configure
PVG-399 configure
AD-310 configure
EP 24V configure
TPS-210 TPS-220 configure
ER-214 configure
TRM-100 configure
XR-4x0 | XR-4x1 configure
ES-20 configure
EF2 24...230 V configure
ZT-S configure
TPS-Serie
Sensors for determining the dew point in a wide range of applications
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Operating conditions
- Temperature: : -40...80°C
- rel. Humidity : 0 - 100% rH
Measuring range
- measuring range (dew point) : -50...+80°C
- measuring range (Temperature) : -40...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V oder 4...20mA
T-200.F Ex
Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Ex-Polyester
- Box : Ex-Aluminium
Properties
- Protection class EN60529 : IP 65
- connection thread : G2"
- Union nut : G 2¾"
- Guide tube length : max. 6 m
- Operating temperature : -20…+60 °C
- Operating pressure : max. 6 bar je nach Ausführung
- media density : ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- Ex-protection : siehe Baumusterprüfbescheinigung
- CE marking : siehe Konformitätserklärung
PVG-399
PVC weight with magnet insert and eyelet for cable fixing
for actuating monostable and bistable contacts
Variants
- 32 : Außen Ø 25 mm x 175 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 32 u. 34 mm bis 6m Länge
- 37 : Außen Ø 30 mm x 170 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 40 mm bis 6m Länge
- 40 : Außen Ø 40 mm x 110 mm ca. 175g, geeignet für Rohraußen Ø 50 mm bis 6m Länge
- 4012 : Außen Ø 40 mm x 110 mm ca. 300g, geeignet für Rohraußen Ø 50 mm bis 12m Länge
- 4016 : Außen Ø 40 mm x 110 mm ca. 360g geeignet für Rohraußen Ø 50 mm bis 16m Länge
- 50 : Außen Ø 50 mm x 130 mm ca. 255g, geeignet für Rohraußen Ø 63 mm bis 6m Länge
- 5012 : Außen Ø 50 mm x 130 mm ca. 300g geeignet für Rohraußen Ø 63 mm bis 12m Länge
- 5016 : Außen Ø 50 mm x 130 mm, ca. 360g, geeignet für Rohraußen Ø 63 mm bis 16m Länge
AD-310
programmable Digital Display
The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel : IP 65
- Operating temperature : – 20...+ 60 °C
- nominal voltage : Weitbereichsnetzteil; 20 V DC ... 230 V AC
- Power consumption : max. ca. 3 VA
- Output contact : 2 Schließer / NO
- Switching voltage : max. 250 V AC, 300 V DC
- Switching current : max. 3 A , DC min. 30 mA
- Switching capacity : max. 50W, 100 VA
- Unregulated auxiliary voltage source : 15...20 V DC / 20 mA
- Display : LED 14 mm, 5-stellig
- Dimensions : 96x48x100 mm
- Weight : ca. 200 g
- Panel cut-out : H:45+0,6mm, B:92+0,8 mm
Equipment
- Measuring input current : 0(4)...20 mA DC
- Measuring input voltage : 0(2)...10 V DC
- Measuring input Potentiometric voltage divider : 1...100 kΩ
- Display : LED 14 mm, 5-stellig
- operation : Folientasten
- Display range : -19999...32000
- data backup : EEPROM
- measurement uncertainty : ±1 % oder ±1 Digit
- analogue output : 0 (4)...20 mA
EP 24V
Plate Electrode as Leak Detector (conductive)
with general approval for constructions Z-65.40-191
Properties
- Protection class EN60529 : IP 68
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- cable length : auf Wunsch
Material
- Cable : TPK (PVC Basis)
- Sensor rods : Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
- cable material : FEP (Teflon) | EX (PVC blau)
TPS-210 TPS-220
Flexible, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-210
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
Properties TPS-220
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (Humidity) : 0…100% rH
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -50...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
ER-214
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
- Weight : ca. 150 g
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
Output
- Contacts : 1 potentialfreie Wechselkontakte pro Kanal
- Switching voltage : min. 5 V | max. 250 V AC | max. 150 V DC
- Switching current : min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
- Switching capacity : min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
- Working / Idle current : umschaltbar
- overvoltage category : EN 61010-1 Kategorie III
TRM-100
Turbidimeter (0...1.000 FNU or 500...4.000 FAU)
The turbidimeter TRM-100 is a compact device for measuring turbidity in liquids. The "turbidity" is measured using the scattered light method (angle 90 degrees) for the turbidity range of < 1,000 FNU (Formazine Nephelometric Units) and the transmitted light method (angle 0 degrees) for the turbidity ranges > 1,000 FAU (Formazine Attenuation Units).
Properties
- Operating pressure : max. 10 bar @ 20 °C | max. 2,5 bar @ 60 °C
- Measuring range : 500...4.000 FNU / FAU
- Measuring accuracy : +/-5 %
- Mounting position : horizontal
- Process connection : DN 20 | DN 40
- Flange connection : >= DN 20
- number of senders : 2
- number of receivers : 1
Material
- Seal : EPDM | optional FPM (Viton)
- Process connection : PVC | PPH
- Measuring tube : Borsilikatglas mit Nano Beschichtung
Input
- Power supply : 18...30 V DC
- Power consumption : < 2 W
Output
- Output contact : 4...20 mA
- Switching delay (adjustable) : 1...10 s
- Protection class : IP 65
- Switching voltage : max. 250 V AC | max. 115 V DC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA, 60 Watt
- Potential-free changeover contact : 1 @ 1...10 s
CSC-20 YUGO
Decentralised control unit, equipped with a CO2 sensor for needs-based ventilation
Decentralised CO2 monitoring with direct control of various supply and exhaust air elements such as fans and dampers (0..10.000 ppm)
Properties
- Power supply : 230 V AC
- measuring range (CO2) : 0..10.000 ppm
- Measuring accuracy CO2 : ± 50ppm +3 % vom Messwert
- Operating conditions : 0…50°C / 0…85 %rH
- Storage conditions : -30…70°C / 0…85 %rH
- Protection class : IP 31
- EMV/ESD : EN 50082-1, EN 50082-2
- Signal output : I²C
XR-4x0 | XR-4x1
Electrode relay with ATEX
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
ES-20
Pressure limiter | Pressure monitor | Safety pressure limiter | Pressure regulator | electronic safety switching device
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
Connections
- Process connection Relative pressure (internal thread) : G ¼“
- Process connection differential pressure (internal thread) : G ⅛“
- Analogue current output : 1 x 4...20 mA
- Digital inputs/outputs (configurable) : 2 x Alarm / 1 x Alarm & 1 x Fernentriegelung
Measuring range relative pressure
- Nominal pressure (variable selectable) : -1...500 bar
- Overload pressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Setting accuracy : 0,1 % vom Nenndruck
Measuring range differential pressure
- Nominal pressure : 0...1 mbar 0...10 mbar 0...50 mbar 0...100 mbar 0...250 mbar 0...1.000 mbar
- Overload pressure : 10 x Nenndruck
- Bursting pressure : 15 x Nenndruck
- Setting accuracy : 0,1 % vom Nenndruck
EF2 24...230 V
Conductive electrodes with 24...230 V direct connection
The EF2 overfill protection (24...230 V AC/DC) is approved by "DIBt" as an overfill protection for liquids hazardous to water.
Properties
- connection : Polyesterdose (PO)
- Protection class : IP 65
- connection thread : G1"
- Union nut : auf Wunsch
Material
- Screw connection : PE, PVC, PPH, PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 100 kΩ
- Sensitivity range : einstellbar 2…100 kΩ
Operating temperature
- PE : atmosphärisch
- PVC : atmosphärisch
- PPH : 90 °C
- PTFE : 100 °C
Power supply
- nominal voltage : 24…230 V AC/DC
- Power consumption : < 2 W
Output
- Output contact : 2 potentialfreie Wechselkontakte
- Switching voltage : max. 250 V AC /30 V DC
- Switching current : max. 5 A AC / 5 A DC
- Switching capacity : max. 750 VA / 90 W
- displays : Betriebs-LED Grün, Funktions-LED Rot
- Switching delay : ca. 0,5 s Anzug / Abfall
- CE marking : siehe Konformitätserklärung
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
- Operating voltage : 12...32 V DC (max. 0,2 W)
- Dimensions : Ø 22 x 59 (D x H), SW22
- Housing : Edelstahl
- Measuring range nominal pressure : -1…500 bar
- Overpressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Protection class : IP65
- Output signal : ZILA-DIO
Operating conditions
- Pressure type : Relativdruck
- Temperature of the fluid : -40 …+125 °C
- fluid temperature (optional) : -20 …+125 °C
- Ambient temperature : -40 …+105 °C
electrical connection
- Standard : Binder M12 x 1
T205-0
Immersible Magnetic Probe made of PVC, PE, PPH, PTFE or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 68 Kabel
- Float type : max. 4x Zylinder Edelstahl 27 mm Ø
- connection cable : 1000 mm PUR Blau
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 120 °C
- Operating pressure : max. 10 bar (Schwimmer)
- media density : 0,78 g/cm³
- Number of contacts : max. 2 Schließer / 2 Öffner
- Switching current : 1A, 2A
- Switching capacity : 50 W/VA
- min. contact distance with several floats : 50 mm
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Polyester junction box :
- Aluminum housing :
- Polyethylene connection head :
- Cable :
- Plug :
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
- Operating temperature : atmosphärisch
- PP : max. 90°C
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!