Cart
product added to request
TK-308 configure
EE-24 configure
MKL configure
KG-2XX configure
HD-110 | HD-112 | HD-114 configure
ZT-S configure
TK-308
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 11,12, 15, 17
- connection cable : 1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating pressure : max. 6 bar
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
Operating temperature
- PVC : max. 60 °C
- PE : max. 80 °C
- PP : max. 90 °C
MaterialDensity
- Type 11 : 0,60 g/cm³
- Type 12 : 1,00 g/cm³
- Type 15 : 0,59 g/cm³
- Type 17 : 0,63 g/cm³
EE-24
Ex-Electrode-single with integrated safety barrier
When using a threshold detection electrode with integrated safety barrier, exceeding or falling below a threshold in conductive fluids in Ex-Zone 0 (category 1) can be detected.
Properties
- connection thread : G 1/2” Standard | G 3/4” | G1”
- Cable : TPK (Standard) | SIL (Silikon) | FEP (Teflon)
- rod length : max. 6.000 mm
- Operating pressure : max. 40 bar
Material
- electrode body : Edelstahl 1.4571
- Process connection : Edelstahl 1.4571
- Coating : PTFE
- electrode rod : Edelstahl 1.4571
- on request : Hastelloy C | Tantal
MKL
Magnetic Flap Indicator
The MKL level indicator is connected by its two connections to the container to be monitored (see connection example). According to the law of interconnected containers the level in the float chamber corresponds exactly to the level in the container
Properties
- connection : Flansch ab DN 15
- Material : rostfreier Edelstahl, PVC, PPH, PVDF
- Material flange : Edelstahl 1.4571, C22.8
- Material Float : Edelstahl, Titan, PVC, PPH, PVDF
- Number of contacts : beliebig
- Contact load : max 10 VA, max 230 V AC
- Display length : max. 6m
Operating temperature
- PTFE seal : max. 150 °C
- Stainless steel: Klingerit seal : max. 200 °C
- PVC : max. 60 °C
- PPH : max. 90 °C
- PVDF : max. 130 °C
Stainless steel float
- Weight : ~ 300 g
- Dimensions : Ø 52 x 270
- Operating pressure : 16 bar
- media density : ρ ≥ 0,70 g/cm³
Stainless steel float
- Weight : ~ 320 g
- Dimensions : Ø 52 x 270
- Operating pressure : 40 bar
- media density : ρ ≥ 0,75 g/cm³
Titanium float
- Weight : ~ 180 g
- Dimensions : Ø 52 x 150
- Operating pressure : 16 / 40 bar
- media density : ρ ≥ 0,73 g/cm³
PVC float
- Weight : ~ 331 g
- Dimensions : Ø 52 x 250
- Operating pressure : 6 bar
- media density : ρ ≥ 0,8 g/cm³
PPH float
- Weight : ~ 283 g
- Dimensions : Ø 52 x 250
- Operating pressure : 6 bar
- media density : ρ ≥ 0,69 g/cm³
PVDF float
- Weight : ~ 352 g
- Dimensions : Ø 52 x 250
- Operating pressure : 6 bar
- media density : ρ ≥ 0,85 g/cm³
KG-2XX
Capacitiv Limit Switch
Capacitive limit switches respond on approach of solid and liquid media.
Properties KG-201
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 110 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 0,55 V A
- Max. switching capacity : 36,3 V A
- Switching distance(mm) : 3...30
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,1 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED rot, eing.
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –25...+70 °C
Properties KG-200|KG-202
- Operating voltage : 20...250 V AC
- Switching version(*standard) : *Schließer | Öffner
- connection : 2-Leiter
- nominal voltage : 220 VAC
- No-load current : typ. 2,5 mA
- Min. switching current : typ. 5 mA
- Max switching current : 330 mA
- Max. Voltage drop with "ON" : typ. 6 V
- Min. switching capacity : 1,1 V A
- Max. switching capacity : 72,6 V A
- Switching distance(mm) : 3...20
- Switching hysteresis : typ. 10%
- Repeatability atTa=const. : typ. 0,5 %
- Drift : < 10%
- Switching frequency : max. 25 Hz
- Switching indicator : LED gelb, intern
- Permanent short-circuit protection : nein
- Permissible ambient temperature : –20...+60 °C
properties KG-211
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...30
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,1%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED rot, eing.
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –25...+70°C
Properties KG-210|KG-212
- Operating voltage : 10...35 V DC
- Permissible ripple : 10 %
- Switching version(*standard) : *Schließer, Öffner
- connection : 3-Leiter
- nominal voltage : 24 V DC
- No-load current : typ. 15 mA
- Max switching current : 400 mA
- Max. Voltage drop with "ON" : 2,5 V
- Max. switching capacity : 14 W
- Switching distance(mm) : 3...25
- Switching hysteresis : < 10%
- Repeatability atTa=const. : < 0,5%
- Drift : < 10%
- Switching frequency : max. 50 Hz
- Switching indicator : LED gelb, intern
- Reverse polarity protection : ja
- Permanent short-circuit protection : ja
- Permissible ambient temperature : –20...+60°C
HD-110 | HD-112 | HD-114
Hydrostatic screw-in probes (4...20mA | 0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : -10...70 °C
- Storage temperature : -25...70 °C
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik | 4...20 mA
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : ca. 20 %
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik AI2o3 96%, Keramik AI2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- connection thread : G ¾“ | G 1 ½“
- Plug : Steckverbindung DIN 43650
KST-20 VENTO CO2
KST-20 Vento with air quality monitoring function
Automatic, controlled ventilation and dehumidification of rooms with the aH-Controlled technology*
Properties
- measuring range (Humidity) : 0…100 % rF,
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- Signal output : I2C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000…1.500 ppm
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertiges ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
Measuring range
- measuring range (Humidity) : 0...100 % rF
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -40...+80 °C
- Measuring accuracy (temperature) : ± 0,2 °C
- measuring range (CO2) : 0…5.000 ppm
- Adjustable limits : 1.000...1.500 ppm
ZT-S
Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
- Operating voltage : 12...32 V DC (max. 0,2 W)
- Dimensions : Ø 22 x 59 (D x H), SW22
- Housing : Edelstahl
- ltdata.MessbereichNenndruck : -1…500 bar
- Overpressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Protection class : IP65
- Output signal : ZILA-DIO
Operating conditions
- Pressure type : Relativdruck
- Temperature of the fluid : -40 …+125 °C
- ltdata.Medientemperatur(optional) : -20 …+125 °C
- Ambient temperature : -40 …+105 °C
electrical connection
- ltdata.Standard : Binder M12 x 1
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!