The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel
:
IP 65
Operating temperature
:
– 20...+ 60 °C
nominal voltage
:
Weitbereichsnetzteil; 20 V DC ... 230 V AC
Power consumption
:
max. ca. 3 VA
Output contact
:
2 Schließer / NO
Switching voltage
:
max. 250 V AC, 300 V DC
Switching current
:
max. 3 A , DC min. 30 mA
Switching capacity
:
max. 50W, 100 VA
Unregulated auxiliary voltage source
:
15...20 V DC / 20 mA
Display
:
LED 14 mm, 5-stellig
Dimensions
:
96x48x100 mm
Weight
:
ca. 200 g
Panel cut-out
:
H:45+0,6mm, B:92+0,8 mm
Equipment
Measuring input current
:
0(4)...20 mA DC
Measuring input voltage
:
0(2)...10 V DC
Measuring input Potentiometric voltage divider
:
1...100 kΩ
Display
:
LED 14 mm, 5-stellig
operation
:
Folientasten
Display range
:
-19999...32000
data backup
:
EEPROM
measurement uncertainty
:
±1 % oder ±1 Digit
analogue output
:
0 (4)...20 mA
T205 PP
Magnetic immersion probes made of PP
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Maximum flexibility for an optimal choice of measuring instrument: The VS-D250 transmitter is compatible with all ViscoScope® sensors of the types VA-100 and VA-300.
Properties
Output card socket
:
2
External input
:
0/4…20 mA | 0/2…10 V DC
Power supply
:
24V DC, 12 W
Dimensions
:
142 x 106 x 73 mm (L x B x H)
Front
:
RS232, MODBUS RTU (Standard)
Display and Operation
Lines
:
4
Pages
:
2
Character set
:
alphanumerisch
Buttons
:
3 (front)
Alarms
system function
:
sensor diagnosis
:
Coil Temperature
:
2 configurable LEDs
:
optional outputs
0/4…20mA | 0/2…10V DC (active)
:
RS232 | RS485
:
2 SPDT-Relays: RS232 | RS485
:
Filter
Moving average (200 measured values)
:
EF2…5 24V
Conductive electrodes with and without 24 V DC direct connection
The conductive electrodes EF2...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
Protection class EN60529
:
IP 65
connection thread
:
G1" | G1¼" | G1½"
Union nut
:
G2¾" | S 100x8
Operating temperature PE / PVC
:
atmospheric
Operating temperature PPH
:
90°C
Operating temperature PTFE
:
100°C
Operating pressure
:
atmospheric
Resistance value of line monitoring
:
22 kΩ / 100 kΩ