XR-6x0 | XR-6x1
Contact protection relay Measuring transducer
The contact protection relays are universal measuring transducers, which
input signals (resistance values) with "Namur" specification (DIN EN 60947).
Namur" specification (DIN EN 60947) into switching signals of floating
output contacts.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V, max. 250 V AC / 150 V DC
- Switching current : min. 5 mA, max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW, max.100 VA / max. 50 W
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Baumusterprüfbescheinigung
- Weight : ca. 170 g
- Quiescent current : umschaltbar
EF2…5 24V
Conductive electrodes with and without 24 V DC direct connection
The conductive electrodes EF2...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- Protection class EN60529 : IP 65
- connection thread : G1" | G1¼" | G1½"
- Union nut : G2¾" | S 100x8
- Operating temperature PE / PVC : atmospheric
- Operating temperature PPH : 90°C
- Operating temperature PTFE : 100°C
- Operating pressure : atmospheric
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- Spacer form length > 1000 mm : 1 per 1000 mm
- rod length : max. 6.000 mm
- Rod diameter : 4mm | 6 mm
Material
- Screw connection : PPH | PE | PVC | PTFE
- Sensor rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- Coating : PTFE
- ltdata. :
BI
Bistable Switch
Properties
- Protection class : IP 65
- Switching current : max. 1 A
- Switching voltage : max. 24 V
- Switching capacity : max. 20 W/VA
Material
- Housing : Messingrohr Ø 10 x 1
- Cable : TPK (PVC basis) | SIL (Silikon)
Operating temperature
- TPK : –15 ° ... + 60 °C
- SIL : –15 ° ... +130 °C
ZT-N
Customisable low pressure sensor for precise measurement of the smallest pressures
Reliable low pressure sensor in a robust and compact design
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
KS-CAN-03
CANopen Climate Transmitter
Climate transmitter KS-CAN-03 for temperature and humidity measurement, according to CAN bus specifications with a digital climate probe
Properties
- Housing : Aluminium, eloxiert
- Measuring element humidity : kapazitiv, betauungsfest
- Measuring element temperature : Halbleiter
- measuring resolution : 12 Bit
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Option : Bereistellung des EDS-Files
tdata.
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Minimum air velocity across the sensor required for measurement : 1,5 m/s
ELH 230 V
Hanging electrode as leakage probe 24...230 V AC/DC
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
QFS-3X
Mercury-free float switch with µ-switch
Properties
- Protection class EN60529 : IP 68
- Cable entry : PVC , PTFE bzw. PVDF
- Conductor cross-section : 3 x 0,75 mm², PUR 3x 0,5mm²
- Operating pressure cylinder : max. 1 bar
- Operating pressure sphere : max. 2 bar
- Switching system : µ-Schalter
- Contact : Wechsler, NO, NC
Material Float
- QFS-30 : PPH (Polypropylen)
- QFS-31 : PPH (Polypropylen)
- QFS-34 : PE (Polyethylen)
Cable
- TPK : PVC Basis Ø 5,9 mm
- TPKV : PVC verstärkt Ø 7,3 mm
- PUR : Polyurethan Ø 5,4 mm
- SIL : Silikon Ø 6,4 mm
- FEP : Teflon Ø 4,0 mm
- AEM : Ethylen-Acrylat-Kautschuk
Cable length between float & attachment
- TPK : 70 mm
- TPKV : 90mm
- PUR : 100mm
- SIL : 80 mm
- FEP : 110 mm
- AEM : abhängig vom Innenkabel
Operating temperature
- TPK(V), AEM : max. + 60 °C
- PUR : max. + 70 °C
- Silicone,Tefloncable with PE float : max. + 80 °C
- Silicone, Teflon cable with PP float : max. + 85 °C
MaterialDensity
- QFS-31 : ≥≥ 0,6 g/cm³
- QFS-34 : ≥≥ 0,75 g/cm³
- QFS-30 TPK(V) cable : ≥≥ 0,85 g/vcm³
- QFS-30 PUR cable : ≥≥ 0,95 g/cm³
- QFS-30 SIL cable : ≥≥ 0,90 g/cm³
- QFS-30 FEP cable : ≥≥ 0,95 g/cm³
- QFS-30AEM cable : ≥≥ 0,90 g/cm³
ER-214
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- Storage temperature : –30...+80 °C
- AC nominal frequency : 48...62 Hz
- Power consumption : max. 1 W / VA
- Weight : ca. 150 g
Input
- Open circuit voltage : ≤ 10 V AC
- Short-circuit current : ≤ 5 mA
Output
- Contacts : 1 potentialfreie Wechselkontakte pro Kanal
- Switching voltage : min. 5 V | max. 250 V AC | max. 150 V DC
- Switching current : min. 5 mA | max. cosφ=1 3A | max. cosφ=0,7 1 A/AC | max. cosφ=1
- Switching capacity : min. 300 mW | max. 750 VA / 150 W (30 V DC / 5 A) / 18 W (150 V DC / 0,12 A)
- Working / Idle current : umschaltbar
- overvoltage category : EN 61010-1 Kategorie III
KST-20 Vento-RN
Climate control with aH-Controlled technology and Rn-Protected seal
The KST-20 Vento/RN is a climate control unit with aH-Controlled technology and Rn-Protected seal for ventilation and dehumidification of all types of private, commercial and industrial rooms. With the three operating modes for ventilation, dehumidification and radon measurement, the KST-20 Vento climate control unit can be used flexibly in almost all living, working and industrial areas.
Properties
- Power supply : 230 V AC
- Protection class : IP 65
- Dimensions (LxBxH) : 160 x 90 x 50 mm
- Housing : hochwertigem ASA+PC (UL 94 V-0) für harte Beanspruchung, flammwidrig und selbstverlöschend
- Signal output : I²C
Measuring range
- measuring range (Humidity) : 0…100 % rF
- Measuring accuracy (humidity) : ±2 %
- measuring range (Temperature) : -40…+80 °C
- Measuring accuracy (temperature) : ±0,2 °C
- measuring range (radon) : 0...1200 Bq/m³
- Adjustable limits : 80...1000 Bq/m³
Our application engineers advise you personally, comprehensively and professionally!