Cart
product added to request
product added to request
EE-2X configure
TK-300 configure
TK-301 configure
T-200.F Ex configure
LU-180 EX configure
TK-303 configure
W-35X configure
QFS-12 configure
T206
Magnetic immersion probes made of PP or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Number of contacts : 1 x Schließer/Öffner durch 180°-Drehung des Schwimmers
- Switching current : 1 A
- Switching capacity : 50 W/VA
T206PP
- Float type : max. 2 x Typ 12 (13)
- max. 2x Type 12(13) : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : 60 °C
- Operating pressure : drucklos
- media density : Typ 12: 0,93 g/cm³ | Typ 13: 0,68 g/cm³
- min. contact distance with several floats : 50 mm
T206VA
- Protection class EN60529 : IP 65
- Float type : max. 2 x Typ 08
- connection cable : PTFE-Litze 0,24 mm²
- Sliding tube length : max. 1000 mm
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar
- media density : Typ 08: 0,78 g/cm³
- min. contact distance with several floats : 42 mm
EE-2X
electrode, multiple for Ex-Zone 0 (Cat. 1)
The conductive electrodes of the EE-21/EE-22 series enable the monitoring of conductive liquids within the Ex area Zone 0 (Cat. 1).
Variants
- cable connection on side : EE-21
- cable connection on top : EE-22
Properties
- connection : Edelstahl (1.4571)
- Protection class EN60529 : IP65
- Ex-protection : TÜV 02 ATEX 1796 X
- Ex protection type : II 1 G Ex ia IIC T6 bzw. Ex ia IIB T6 / II ½ G Ex ia IIC T6 bzw. Ex ia IIB T6
- connection thread : G1" | G1¼"
- Cable entry EE-21 : Edelstahl (1.4571)
- Cable entry EE-22 : Kunststoff
- Rod diameter : 4 mm | 6 mm
- rod length : max. 6.000 mm
- Operating pressure media side : max. 40 bar
- Spacer : ab Länge > 1000 mm je 1 pro 1000 mm
Material
- electrode body : Edelstahl (1.4571)
- Seal (head) : Viton
- Seal (media side) : Viton | PTFE
- Potential equalisation conductor connection : Edelstahl (1.4571)
- electrode rods : Edelstahl (1.4571) | Hastelloy C | Tantal
- Coating : PTFE
Operating temperature
- Category 1 Class T6...T1 : 60 °C
- Category 2 Class T6 : 80 °C
- Category 2 Class T5 : 95 °C
- Category 2 Class T4 : 130 °C (100°C)
- Category 2 Class T3...T1 : 150 °C (100°C)
TK-300
Level transducer
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Properties TK-300
- connection : Polyesterdose | Aluminiumdose | Stecker nach DIN 43650
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 10 (14)
- connection cable : 1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating pressure : max. 6 bar
- Resolution : 10 mm, 15 mm oder 1%, 2%, 5% je nach Auflösung
- CE marking : siehe Konformitätserklärung
Operating temperature
- PV : max. 60°C
- PE : max 80 °C
- PP : max. 90°C
MaterialDensity
- Type 10 : 0,72 g/cm³
- Type 14 : 0,72 g/cm³
- Type 18 : 0,82 g/cm³
TK-301
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 05 (06)
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Operating pressure : max. 20 bar
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm| 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 05 : 0,81 g/cm³
- Type 06 : 0,67 g/cm³
T-200.F Ex
Overfill protection for containers with Ex approval
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Box : Ex-Polyester
- Box : Ex-Aluminium
Properties
- Protection class EN60529 : IP 65
- connection thread : G2"
- Union nut : G 2¾"
- Guide tube length : max. 6 m
- Operating temperature : -20…+60 °C
- Operating pressure : max. 6 bar je nach Ausführung
- media density : ρ ≥ 0,72 g/cm³ (je nach Schwimmertyp)
- Switching hysteresis : 2 mm
- Switching point tolerance : max. 2 mm
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- Ex-protection : siehe Baumusterprüfbescheinigung
- CE marking : siehe Konformitätserklärung
LU-180 EX
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
TK-303
Level transmitter for Ex-Zone 0 (Cat.1)
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class : IP 65
- Float type : 03, 04, 09
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar (Kugel) max. 15 bar (Zylinder)
- Resolution : 7,5 mm | 10 mm
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 03 : 0,75 g/cm³
- Type 04 : 0,65 g/cm³
- Type 09 : 0,76 g/cm³
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
- details : folgen
W-35X
Water Level Gauge with sight glass indicator
The water level gauge is particulary suitable for all liquid media which are aggressively hot and rapidly moved in a container, but are not too much contamined.
Properties
- Tank connection : Flansch ab DN 25 oder Verschraubung ab G ½"
- Material Float : PPH max. 2,5 bar, Glas max. 10 bar
- cable length : bei monostabilem Kontakt: Standard 2 m
- Number of contacts : beliebig
- Contact distance : min. 10 mm
- Temperature of the fluid : mit Plexiglasrohr max. +70 °C
- media density : ρ ≥ 0,95 g/cm³ | ρ ≥ 0,85 g/cm³ (auf Wunsch)
Properties W-350
- Material tube sight glass : transparentes PVC
- Temperature of the fluid : max. +60 °C
- Operating pressure : max. 2,5 bar
- Material flange : PVC
- Material connection with angle valve : PVC
- Material sealing ring : Gummi
Properties W-351
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Rotguss
- Material connection with angle valve : Rotguss
- Material sealing ring : Silikon
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
Properties W-352
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Edelstahl
- Material connection with angle valve : Edelstahl 1.4571 als Bogen 90°
- Material sealing ring : PTFE und Viton
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
Properties W-353
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Edelstahl
- Material connection with angle valve : Edelstahl 1.4401
- Material sealing ring : PTFE und Viton
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
ZDT-N
Differential pressure transmitter for low pressure applications
Versatile and reliable differential pressure transmitter for measurement on air and other non-aggressive media.
Properties
- Pressure type : Differenzdruck
- Housing : Kunststoff mit LCD-Anzeige (optional)
- Overpressure : 2,5* x Nenndruck
Measurement parameters
- Total error : ± 2,5 % FS (typ. ± 0,5 %)
- Linearity error : ± 1 % FS
- Signal output selection : 0...10 V 4...20 mA
- Pressure ranges (mbar) : 1/ 2 / 4 – 2,5 / 5 /10 – 12,5 / 25 /50 – 50 / 100 /200
Operating conditions
- Operating voltage (0...10V) : 14...30 V DC
- Operating voltage (4...20mA) : 12...30 V DC
- Operating temperature : 0...+50 °C
- Storage temperature : -20°C...+120°C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 3,5 mm oder 5,5 mm
Pressure measuring ranges
- 1/2/4mbar :
- 2,5/5/10mbar :
- 12,5/25/50mbar :
- 50/100/200mbar :
- other on request :
QFS-12
Two-Point Float-Switch
With the two-point float switch Type QFS-12 can be realized pump controls in liquid media on a simple way.
Properties
- Protection class EN60529 : IP68
- Side installation : PVC-Stopfbuchsverschraubung G 2”
- Installation from above : PVC-Stopfbuchsverschraubung G 2”
- Operating pressure : max. 2 bar
- Contact : Wechselkontakt
- Switching voltage : 4....250 V AC / DC
- Switching current : 1mA.....1A
- Switching capacity : 60W/VA
- media density : ρ ≥ 0,9 g/cm³ bis ρ ≥ 0,8 g/cm³
- Material Float : Polyethylen
Cable
- TPK : PVC Basis
- TPKV : PVC Basis verstärkt
- PUR : Polyurethan
- NEO : Neopren
- SIL : Silikon
- FEP : Teflon
- AEM : Ethylen-Acrylat-Kautschuk
Operating temperature
- TPK(V), NEO, AEM : max.+60 °C
- PUR : max.+70 °C
- FEP, SIL : max.+80 °C
Our application engineers advise you personally, comprehensively and professionally!