with general approval for constructions Z-65.40-191
Properties
Protection class EN60529
:
IP 68
Operating temperature
:
atmosphärisch
Operating pressure
:
atmosphärisch
Resistance value of line monitoring
:
22 kΩ / 100 kΩ
cable length
:
auf Wunsch
Material
Cable
:
TPK (PVC Basis)
Sensor rods
:
Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
cable material
:
FEP (Teflon) | EX (PVC blau)
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
MKL
Magnetic Flap Indicator
The MKL level indicator is connected by its two connections to the container to be monitored (see connection example). According to the law of interconnected containers the level in the float chamber corresponds exactly to the level in the container
Properties
connection
:
Flansch ab DN 15
Material
:
rostfreier Edelstahl, PVC, PPH, PVDF
Material flange
:
Edelstahl 1.4571, C22.8
Material Float
:
Edelstahl, Titan, PVC, PPH, PVDF
Number of contacts
:
beliebig
Contact load
:
max 10 VA, max 230 V AC
Display length
:
max. 6m
Operating temperature
PTFE seal
:
max. 150 °C
Stainless steel: Klingerit seal
:
max. 200 °C
PVC
:
max. 60 °C
PPH
:
max. 90 °C
PVDF
:
max. 130 °C
Stainless steel float
Weight
:
~ 300 g
Dimensions
:
Ø 52 x 270
Operating pressure
:
16 bar
media density
:
ρ ≥ 0,70 g/cm³
Stainless steel float
Weight
:
~ 320 g
Dimensions
:
Ø 52 x 270
Operating pressure
:
40 bar
media density
:
ρ ≥ 0,75 g/cm³
Titanium float
Weight
:
~ 180 g
Dimensions
:
Ø 52 x 150
Operating pressure
:
16 / 40 bar
media density
:
ρ ≥ 0,73 g/cm³
PVC float
Weight
:
~ 331 g
Dimensions
:
Ø 52 x 250
Operating pressure
:
6 bar
media density
:
ρ ≥ 0,8 g/cm³
PPH float
Weight
:
~ 283 g
Dimensions
:
Ø 52 x 250
Operating pressure
:
6 bar
media density
:
ρ ≥ 0,69 g/cm³
PVDF float
Weight
:
~ 352 g
Dimensions
:
Ø 52 x 250
Operating pressure
:
6 bar
media density
:
ρ ≥ 0,85 g/cm³
Our application engineers advise you