Cart
EE-24 configure
TK-308 configure
OAA-300 configure
ViscoScope® VA-300 configure
TPS-210 TPS-220 configure
EP 24V configure
LU-1X0 configure
W-35X configure
EE-24
Ex-Electrode-single with integrated safety barrier
When using a threshold detection electrode with integrated safety barrier, exceeding or falling below a threshold in conductive fluids in Ex-Zone 0 (category 1) can be detected.
Properties
- connection thread : G 1/2” Standard | G 3/4” | G1”
- Cable : TPK (Standard) | SIL (Silikon) | FEP (Teflon)
- rod length : max. 6.000 mm
- Operating pressure : max. 40 bar
Material
- electrode body : Edelstahl 1.4571
- Process connection : Edelstahl 1.4571
- Coating : PTFE
- electrode rod : Edelstahl 1.4571
- on request : Hastelloy C | Tantal
TK-308
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 11,12, 15, 17
- connection cable : 1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating pressure : max. 6 bar
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
Operating temperature
- PVC : max. 60 °C
- PE : max. 80 °C
- PP : max. 90 °C
MaterialDensity
- Type 11 : 0,60 g/cm³
- Type 12 : 1,00 g/cm³
- Type 15 : 0,59 g/cm³
- Type 17 : 0,63 g/cm³
OAA-300
Alarm Indicator (Measuring Transducer) with general approval for construction
Our alarm indicators type OAA-300 are stand-alone signaling devices with optic and acoustic alarm indication.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : – 20…+60 °C
- Storage temperature : – 30…+80 °C
- Sensitivity : bei konduktiver Messung: 3, 10, 30, 100kΩ
- Dimensions : 170 x 190 x 85 mm
- Weight : ca. 0,8 kg
Control circuits
- Open circuit voltage : max. 10 V DC
- Short-circuit current : max. 10 mA
- Switching delay : ca. 0,5 s
Power supply
- nominal voltage : 230 V AC (optional 24, 115, 240 V AC 24 V DC
- Nominal frequency : 48...62 Hz
- Power consumption : max. 3 W/VA
Output
- Switching voltage : max. 250 V
- Switching current : max. 3 A
- Switching capacity : max. 500 VA | max. 50 W
- Volume : 75 dB
ViscoScope® VA-300
Maintenance-free inline process viscometer for real-time viscosity measurement
The ViscoScope® sensors are made of high-quality, first-class stainless steel and impress with their intelligent, robust design.
Properties
- Protection class : IP65
- Material : 1.4571 / 1.4404 (316Ti / 316L)
- Process temperature : -40°C … +450°C
- Process pressure : Vakuum ... 450 bar
- Process connections : DIN Flansch | ANSI Flansch | NPT | Varivent® | Tri-Clamp
- Cable length sensor - transmitter : max. 1.000m
- max. flow velocity : 10 m / sec
- Ex approval : (optional) II 1/2G Ex ia IIC T6...T3 Ga/Gb
- Material (optional) : Hastelloy C22, Duplex 2205, Teflon
Sensor types
- big cylinder : VA-300L
- small cylinder : VA-300M
- Sphere : VA-300H
- small sphere : VA-300X
Measuring range
- VA-300L : 0,1 - 2.500 mPa·s x g/cm³
- VA-300M : 1 - 25.000 mPa·s x g/cm³
- VA-300H : 100 - 250.000 mPa·s x g/cm³
- VA-300X : 100 - 2.500.000 mPa·s x g/cm³
Probe dimensions
- VA-300L : Ø 32 x 190 mm
- VA-300M : Ø 32 x 165 mm
- VA-300H : Ø 32 x 130 mm
- VA-300X : Ø 19 x 115 mm
TPS-210 TPS-220
Flexible, analogue dew point sensor
The dew point sensors of the enable direct measurement of the dew point and ambient temperature indoors and outdoors.
Properties TPS-210
- Operating voltage : 12...30V DC
- Power consumption : < 15mA
Properties TPS-220
- Operating voltage : 24V DC
- Loop voltage min: : Bürde(Ohm) *0,02 + 8 V
- Loop voltage max: : 30V
General properties
- Housing : Aluminium, eloxiert
- Dimensions (in mm) : 135 x Ø 19,2
Measuring range
- measuring range (Humidity) : 0…100% rH
- Measuring accuracy (humidity) : ± 2%
- measuring range (Temperature) : -50...+80°C
- Measuring accuracy (temperature) : ± 0,2°C
- Signal output : 0...10V | 4...20mA
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- ltdata.Polyesterdose :
- ltdata.Aluminiumdose :
- ltdata.Polyethylenanschlusskopf :
- Cable :
- Plug :
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
- Operating temperature : atmosphärisch
- ltdata.BetriebstemperaturPP : max. 90°C
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
EP 24V
Plate Electrode as Leak Detector (conductive)
with general approval for constructions Z-65.40-191
Properties
- Protection class EN60529 : IP 68
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
- cable length : auf Wunsch
Material
- Cable : TPK (PVC Basis)
- Sensor rods : Edelstahl (1.4571) | Hastelloy B | Hastelloy C | Titan | Tantal | Glaskohlenstoff
Options
- cable material : FEP (Teflon) | EX (PVC blau)
LU-1X0
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
W-35X
Water Level Gauge with sight glass indicator
The water level gauge is particulary suitable for all liquid media which are aggressively hot and rapidly moved in a container, but are not too much contamined.
Properties
- Tank connection : Flansch ab DN 25 oder Verschraubung ab G ½"
- Material Float : PPH max. 2,5 bar, Glas max. 10 bar
- cable length : bei monostabilem Kontakt: Standard 2 m
- Number of contacts : beliebig
- Contact distance : min. 10 mm
- Temperature of the fluid : mit Plexiglasrohr max. +70 °C
- media density : ρ ≥ 0,95 g/cm³ | ρ ≥ 0,85 g/cm³ (auf Wunsch)
Properties W-350
- Material tube sight glass : transparentes PVC
- Temperature of the fluid : max. +60 °C
- Operating pressure : max. 2,5 bar
- Material flange : PVC
- Material connection with angle valve : PVC
- Material sealing ring : Gummi
Properties W-351
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Rotguss
- Material connection with angle valve : Rotguss
- Material sealing ring : Silikon
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
Properties W-352
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Edelstahl
- Material connection with angle valve : Edelstahl 1.4571 als Bogen 90°
- Material sealing ring : PTFE und Viton
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
Properties W-353
- Material tube sight glass : Hartglas, Plexiglas
- Temperature of the fluid : max. +120 °C
- Material flange : Edelstahl
- Material connection with angle valve : Edelstahl 1.4401
- Material sealing ring : PTFE und Viton
- Operating pressure with glass tube : max. 10 bar
- Operating pressure with plexiglass tube : max. 2 bar
T205 PP
Magnetic immersion probes made of PP
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Protection class : IP 65
- Number of floats : 1x Typ 12 | 1x Typ 13
- connection cable : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : max. 60 °C
- Operating pressure : drucklos
- Number of contacts : 1x Schließer / Öffner
- Switching current : 1 A
- Switching voltage : 250 V AC
- Switching capacity : 50 W/VA
Float type
- Type 12 : Zylinder PP 19 mm Ø | Dichte 0,93 g/cm³
- Type 13 : Zylinder PP 25 mm Ø | 0,68 g/cm³
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!