CO2 sensor for measuring room air quality with visual and acoustic warning signal output
Multifunctional CO2 sensor with LED display and acoustic alarm, equipped with switching functions for both industrial and private applications (0...3.000ppm)
Product features
Product type
:
CO2-Sensor zur Bewertung und Überwachung der Luftgüte
Measuring principle
:
Basierend auf optischem Messprinzip (NDIR)
Measuring range
:
Lieferbar in unterschiedlichen Messbereichen (Standard 0…3.000ppm)
Display
:
Darstellung der CO2-Konzentration mittels Bargraphanzeige (Luftgüteampel)
Accuracy
:
+-3% vom Messbereich (30 ppm bei 3.000 ppm)
Relay output:
:
Potentialfrei
Response time
:
ca. 20 s
Operating voltage
:
24 V DC, 150 mA
MTA
Mechanical tank level indicator
The tank level indicator is a mechanically actuated indication operating "on the spot”. It permits a high degree of safety and flexibility thanks to separate points of measurement and indication.
Properties
Tank connection
:
Flansch ab DN 80 (Sonderanschlüsse auf Wunsch)
Material
:
siehe Maßbild
Material Tube
:
PVC, transparent | Ø 50 x 1,8 | Ø 63 x 3,0
Operating temperature
:
–20...+60 °C
Operating pressure
:
atmosphärisch
Material Float
PPH
:
Ø 70 mm 460 g
PVC
:
Ø 70 mm 455 g
PPH
:
Ø 40 mm 370g
PE
:
Ø 70 mm ca. 450 g
Material Rope
PPH
:
(rot, Ø 2 mm) ~ 2 g/m
Polyester
:
(bunt, Ø 2 mm) ~ 4 g/m
PTFE
:
(weiss, Ø 3 mm) ~ 10 g/m
ZDT-Serie
Differential pressure transmitter for high or low pressure applications
Versatile and reliable differential pressure transmitter for measuring air, non-aggressive media as well as liquids and oils.
Properties
Pressure type
:
Differenzdruck
Housing
:
Kunststoff
LCD display
:
optional
Signal output
:
0…10 V | 4…20 mA
Measurement parameters
Total error
:
± 2,5 % FS (typ. ± 0,5 %)
Linearity error
:
± 1 % FS
Operating conditions
Operating temperature
:
0...+50 °C
Storage temperature
:
-20°C...+120°C
OAA-300
Alarm Indicator (Measuring Transducer) with general approval for construction
Our alarm indicators type OAA-300 are stand-alone signaling devices with optic and acoustic alarm indication.
Properties
Protection class EN60529
:
IP 65
Operating temperature
:
– 20…+60 °C
Storage temperature
:
– 30…+80 °C
Sensitivity
:
bei konduktiver Messung: 3, 10, 30, 100kΩ
Dimensions
:
170 x 190 x 85 mm
Weight
:
ca. 0,8 kg
Control circuits
Open circuit voltage
:
max. 10 V DC
Short-circuit current
:
max. 10 mA
Switching delay
:
ca. 0,5 s
Power supply
nominal voltage
:
230 V AC (optional 24, 115, 240 V AC 24 V DC
Nominal frequency
:
48...62 Hz
Power consumption
:
max. 3 W/VA
Output
Switching voltage
:
max. 250 V
Switching current
:
max. 3 A
Switching capacity
:
max. 500 VA | max. 50 W
Volume
:
75 dB
Our application engineers advise you