Functionally safe pressure transmitter for ES series
Reliable pressure measurement and optimal process monitoring thanks to the ZT series. Developed for high demands and safety-critical applications
Properties
- Operating voltage : 12...32 V DC (max. 0,2 W)
- Dimensions : Ø 22 x 59 (D x H), SW22
- Housing : Edelstahl
- Measuring range nominal pressure : -1…500 bar
- Overpressure : 2 x Nenndruck
- Bursting pressure : 4 x Nenndruck
- Protection class : IP65
- Output signal : ZILA-DIO
Operating conditions
- Pressure type : Relativdruck
- Temperature of the fluid : -40 …+125 °C
- fluid temperature (optional) : -20 …+125 °C
- Ambient temperature : -40 …+105 °C
electrical connection
- Standard : Binder M12 x 1
TK-313
Evaluation unit with 2 change over limit contacts
The TK-313 limit comparator can be used in conjunction with our
TK-30... continuous level sensors with 0(4)...20 mA or 0...10 V output
signal for level control / measurement.
Properties
- Protection class EN60529 clamp : IP 20
- Protection class EN60529 front panel housing : IP 40
- Operating temperature : –20...+60 °C
- nominal voltage : 24... 230 V AC/DC
- Power consumption : 2 VA
- Dimensions housing type B : 22,5 x 114,5 x 99
- Dimensions housing type C : 22,5 x 114,5 x 114
Input
- power : 0/4...20 mA
- Voltage : 0...10 V
- Resistance in three-wire circuit RG : 0–4...10 kΩ
Output
- Output contacts : 2 Wechselkontakte
- Switching voltage : max. 250 V AC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA
- Temperature influence tolerance : max. ± 0,6 % der Signalspanne
- Mounting : Tragschiene nach EN 50022
- Current output : 4...20 mA bezogen auf die Masse des Eingangs
- Display (%) : 2-stellig, 7-Segment
- Weight : 175 g
- ltdata. :
ZT-V
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Connection
- Signal output : 0...10 V, 3-Leiter | 0,5...4,5, ratiometrisch | 4...20 mA, 2-Leiter
- Electrical connection : DIN EN 175301-803 A | DIN EN 175301-803 C | Binder M12x1 (Serie 713)
- Process connection : G 1/4" ISO 1179-2 (Male Form E) | 1/4" NPT | 7/16" 20 UNF Male
- measuring range (bar) : 0…0,6 | 0…600
Properties
- Pressure type : Relativdruck | Absolutdruck
- Housing : Edelstahl
- Overpressure : 1,5* fach bis 400 bar, darüber 1,2* fach
- Bursting pressure : 3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
- response time : < 1 ms
- Total error : ≤ 0,5 % FS
- Non-linearity : ≤ 0,2 % FS
- Non-repeatability : ≤ 0,10 % FS
- Hysteresis : ≤ 0,15 % FS
ambient conditions
- Temperature of the fluid : -40...+125 °C (0...+80 °C kompensierter Bereich)
- Ambient temperature : -40...+105 °C
- Storage temperature : -40°C...+125°C
- Shock resistance : g 1000 gemäß IEC 60068-2-32
- Vibration resistance : g 20 gemäß IEC 60068-2-6
HD-110 | HD-112 | HD-114
Hydrostatic screw-in probes (4...20mA | 0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : -10...70 °C
- Storage temperature : -25...70 °C
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik | 4...20 mA
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : ca. 20 %
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik AI2o3 96%, Keramik AI2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- connection thread : G ¾“ | G 1 ½“
- Plug : Steckverbindung DIN 43650
T206
Magnetic immersion probes made of PP or stainless steel (1.4571)
Magnetic immersion probes for use with highly aggressive liquid media for detecting level limits in containers
Properties
- Number of contacts : 1 x Schließer/Öffner durch 180°-Drehung des Schwimmers
- Switching current : 1 A
- Switching capacity : 50 W/VA
T206PP
- Float type : max. 2 x Typ 12 (13)
- max. 2x Type 12(13) : LiYY-Kabel 0,14 mm² | PVC-Litze 0,24 mm²
- Operating temperature : 60 °C
- Operating pressure : drucklos
- media density : Typ 12: 0,93 g/cm³ | Typ 13: 0,68 g/cm³
- min. contact distance with several floats : 50 mm
T206VA
- Protection class EN60529 : IP 65
- Float type : max. 2 x Typ 08
- connection cable : PTFE-Litze 0,24 mm²
- Sliding tube length : max. 1000 mm
- Operating temperature : max. 100 °C
- Operating pressure : max. 10 bar
- media density : Typ 08: 0,78 g/cm³
- min. contact distance with several floats : 42 mm
ZCS-5000
Self-contained CO2 sensor ZCS-5000 in small housing with warning horn
stand alone CO2 sensor for measuring and monitoring carbon dioxide concentration in ambient air.
Properties
- Housing : Kunststoff
- Power supply 24V : 24V DC | 230V
Measuring element and parameter
- Measuring principle : optisch, NDIR
- measuring grid : 2 sec.
- Accuracy : ± (50ppm+3% vom Messwert) im Bereich von 300…5.000ppm CO2
Operating conditions
- Operating temperature : 0…+50 °C
- Storage temperature : -30 °C…+75 °C
- Operating humidity : 0…85% rH (nicht kondensierend)
- Storage humidity : 0…85% rH (nicht kondensierend)
T203.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Properties
- Protection class : IP 65 Dose
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 135 °C
- Operating pressure : max. 20 bar
- F-Contact : 1/12 kΩ
- Switching current : 1A, 2A
- Switching voltage : 230 V AC
Float
- quantity : max. 6
- Type 05 : Oval Edelstahl 76 mm Ø | Dichte 0,81 g/cm³
- Type 06 : Oval Edelstahl 90 mm Ø | Dichte 0,67 g/cm³
- Minimum contact distance : Typ 05: 110 mm | Typ 06: 135 mm
Switching contacts and switching capacity
- Changeover contact : max. 5x | 60 W/VA
- normally open : max. 6x | 100 W/VA
- Normally closed contact : max. 4x | 60 W/VA
LU-180 EX
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
ZMF-200e-IR
Robust gas sensor for industrial applications with extended operating temperature range and wide-ranging approvals
The ZMF-20X series includes sensors & transmitters for measuring gas concentrations of various gases such as CO2, methane, propane and SF-6.
This makes the sensors suitable for many applications. The ZMF-20X gas sensors are designed to be extremely rugged & suitable for use
in harsh environments.
Properties
- Operating conditions : -40 °C…+60 °C
- Storage conditions : -40 °C…+85 °C
- RelativeHumidity : 0…95 % nicht kondensierend
- Measurement method : NDIR (dual beam technology)
- Signal output : 4..20mA
- Power supply : 12…24 V DC
- Housing : Edelstahl
- Standard cable length : 1,5 m
- Certification : SIL2, ATEX (optional)
- pressure conditions : 800...1200 mbar
- screw thread : M46x1,5
Measuring ranges
- in ppm : in vol%
- 0…2.000ppm : 0…0,2 % vol
- 0…5.000ppm : 0…0,5 % vol
- 0…10.000ppm : 0…1 % vol
- 0…20.000ppm : 0…2 % vol
- 0…50.000ppm : 0…5 % vol
- 0…200.000ppm : 0…20 % vol
- 0…1.000.000ppm : 0…100 % vol
Measuring Accuracy
- below 25% of the range : ±1 % FS
- below 50% of the range : 2 % FS
- above 50% of the range : ±5 % FS
ELH
Suspension electrode as leakage probe
The leakage probes of the type series ELH are approved by the "DIBt" for the monitoring of collecting chambers, collecting devices, inspection and filling shafts.
General data
- Protection class : IP 68
- Probe body material : PE, PVC, PPH, PVDF
- Diameter probe body : 15 mm, 25 mm, 40 mm
- Operating temperature : atmosphärisch
- Operating pressure : atmosphärisch
- Resistance value of line monitoring : 22 kΩ / 100 kΩ
Material
- Screw connection : PVDF
- Cable : TPK ( PVC Basis)
- on request : FEP (Teflon), PVC - blau
- cable length : auf Wunsch (Standard 3 m)
- Material Sensor rods : Edelstahl (1.4571), Hastelloy B, Hastelloy C, Titan, Tantal, Glas-Kohlestifte
Smart Pressostat App
App for control of ES-2X devices over Bluetooth
Android app for Bluetooth communication between smartphone or tablet and electronic safety switching devices from Fluid.iO
Properties
- platform : Android
- Android Version : 12
QFS-40
Built-in float level switch
The QFS-40 built-in float switch is designed for low-cost monitoring of liquids in containers.
Technical Data
- Switch housing : PPH| PVDF
- Seal : NBR (PPH) | FPM (PVDF)
- Operating temperature : PPH max. 80 °C| PVDF max. 100 °C
- Operating pressure : max. 10 bar
- Mounting position : horizontal (±30° von der Horizontalen)
- Contact assembly : Schliesser-, Öffnerkontakt (je nach Einbau)
- Electrical connection : PVC-Kabel
- Switching capacity : max. 230 V AC/DC| max. 40 VA, max. 2 A
- Contact resistance : max. 80 mW
- Min. electric strength : 400 V DC / 1 s
- Inductive/capacitive loads : Unbedingt Kontaktschutz vorsehen
- fluid density : PPH > 0,6 kg/dm³ | PVDF > 0,95 kg/dm³
- Protection class : IP 68
Connections
- external installation : G ½"
- internal installation : M16
GSB-390
Glass float with magnet insert
for actuating monostable and bistable contacts
Variants
- 150 : AußenØ 26,5 x 150 mm (2 Magnete für monostabile Kontakte) Gewicht ca. 50 g
- 190 : AußenØ 26,5 x 190 mm (2 Magnete für monostabile Kontakte) Gewicht ca. 61 g
- 205 : AußenØ 26,5 x 205 mm (3 Magnete auch für bistabile Kontakte) Gewicht ca. 69 g
EF 3…5 24 V
Conductive electrodes with 24 V DC direct connection
The conductive electrodes EF3...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
- connection : integrierter Anschlusskopf
- Protection class : IP 65
- connection thread : G 1¼"
- Material Screw connection : PPH
- Material electrode rods : Edelstahl (1.4571), Hastelloy C, Titan, Tantal
- material coating : PTFE
- Coating length : voll = ganzer Stab (10 mm am Stabende sind blank) teil = ca. 250 mm von oben
- Rod diameter : 4 mm, 6 mm
- rod length : max. 6 m
- Operating temperature : 85 °C
- Operating pressure : atmosphärisch
- Spacer : ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Properties electronic part
- Operating temperature : –20...+85 °C
- Storage temperature : –30...+85 °C
- nominal voltage : 24 V DC ± 15%
- Power consumption : max. 2 W (Klemme A1, A2)
- Switching voltage : max. 250 V AC, 150 V DC min. 5 V DC (Relais mit Kombi-Goldkontakten)
- Switching current : max. 3 A AC, 3 A DC min. 1 mA
- Switching capacity : max. 750 VA, 150 W
- Sensitivity : 3k ... 100 kΩ in vier Stufen (3 k, 10 k, 30 k, 100 kΩ) wählbar
ER-Serie
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- details : folgen
LGW-13
CO2 sensor for measuring room air quality with visual and acoustic warning signal output
Multifunctional CO2 sensor with LED display and acoustic alarm, equipped with switching functions for both industrial and private applications (0...3.000ppm)
Product features
- Product type : CO2-Sensor zur Bewertung und Überwachung der Luftgüte
- Measuring principle : Basierend auf optischem Messprinzip (NDIR)
- Measuring range : Lieferbar in unterschiedlichen Messbereichen (Standard 0…3.000ppm)
- Display : Darstellung der CO2-Konzentration mittels Bargraphanzeige (Luftgüteampel)
- Switching output : Einstellbarer potentialfreier Schaltausgang
- Signal output : 4...20 mA und 0...10 V Signalausgang (nur bei der Variante L)
- Alarm : Akustischer Alarmmelder (je nach eingestellten CO2-Grenzwerten)
- further function : Integrierte Funktionsüberwachung
- Housing : Kompaktes IP 20 Wandgehäuse (Polycarbonat, weiß)
- Extension : Mögliche Erweiterung um Temperaturmessung
- Assembly : Erhältlich als Tischgerät mit Netzteil oder zur Wand- & Aufputzmontage ohne Netzteil
Technical specifications
- Standard measuring range: : 0…3.000ppm
- Optional measuring ranges: : 0…1% vol, 0…3% vol (weitere auf Anfrage)
- Accuracy : +-3% vom Messbereich (30 ppm bei 3.000 ppm)
- Relay output: : Potentialfrei
- Response time : ca. 20 s
- Operating voltage : 24 V DC, 150 mA
QFS-3X
Mercury-free float switch with µ-switch
Properties
- Protection class EN60529 : IP 68
- Cable entry : PVC , PTFE bzw. PVDF
- Conductor cross-section : 3 x 0,75 mm², PUR 3x 0,5mm²
- Operating pressure cylinder : max. 1 bar
- Operating pressure sphere : max. 2 bar
- Switching system : µ-Schalter
- Contact : Wechsler, NO, NC
Material Float
- QFS-30 : PPH (Polypropylen)
- QFS-31 : PPH (Polypropylen)
- QFS-34 : PE (Polyethylen)
Cable
- TPK : PVC Basis Ø 5,9 mm
- TPKV : PVC verstärkt Ø 7,3 mm
- PUR : Polyurethan Ø 5,4 mm
- SIL : Silikon Ø 6,4 mm
- FEP : Teflon Ø 4,0 mm
- AEM : Ethylen-Acrylat-Kautschuk
Cable length between float & attachment
- TPK : 70 mm
- TPKV : 90mm
- PUR : 100mm
- SIL : 80 mm
- FEP : 110 mm
- AEM : abhängig vom Innenkabel
Operating temperature
- TPK(V), AEM : max. + 60 °C
- PUR : max. + 70 °C
- Silicone,Tefloncable with PE float : max. + 80 °C
- Silicone, Teflon cable with PP float : max. + 85 °C
MaterialDensity
- QFS-31 : ≥≥ 0,6 g/cm³
- QFS-34 : ≥≥ 0,75 g/cm³
- QFS-30 TPK(V) cable : ≥≥ 0,85 g/vcm³
- QFS-30 PUR cable : ≥≥ 0,95 g/cm³
- QFS-30 SIL cable : ≥≥ 0,90 g/cm³
- QFS-30 FEP cable : ≥≥ 0,95 g/cm³
- QFS-30AEM cable : ≥≥ 0,90 g/cm³
HD-1XX
Hydrostatic filling level measurement
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
BK-3X0
Bistable change-over contact
Magnetically actuated changeover switch,
which permanently changes its electrical switching state as a result of a magnetic system passing by, depending on the direction of movement.
Properties
- Protection class EN60529 : IP 65
- Operating temperature : –25...+70 °C
- Wire cross-section max. : 1,5mm²
- Switching point distance between two contacts : min. 40 mm
- Switching hysteresis : ca. 10-15 mm
Material
- Housing : Polycarbonat
- Mounting clip : V2A, Kabelbinder (PP)
- Rivet : V2A
- Screw connection : M 20 x 1.5, Polyamid
Weight
- BK-390-50 : 137 g
- BK-390-63 / BK-380 : 140 g
Switching contact
- Switching voltage : 5...250 V AC/DC
- Switching current : 1mA...6 A AC/DC
- Switching capacity(min.) : 300 VA, 60 W
- Switching capacity(max.) : 5 mW
TK-301
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 05 (06)
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Operating pressure : max. 20 bar
- Resolution : 7,5 mm | 10 mm | 15 mm | 20 mm| 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 05 : 0,81 g/cm³
- Type 06 : 0,67 g/cm³
ZDS-N
Precision pressure switch for low pressure applications
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
technical properties
- Pressure range : 0...500mbar gestuft
- supply : 12 - 24 V DC
- Output : Relais 230 V/1A
- overload : 2 x Messbereich
- Med. connection : Schlauch
- electrical connection : Schraubklemme
- feature : Tasten, LCD-Anz.