Compact sensors for temperature & humidity measurement
The KS series sensors are modular temperature and humidity measurement sensors in compact housings for use in almost any application.
Properties KS-210
Operating voltage
:
12...30V DC
Power consumption
:
< 15mA
Properties KS-220
Operating voltage
:
24V DC
Loop voltage min:
:
Bürde(Ohm) *0,02 + 8 V
Loop voltage max:
:
30V
General properties
Housing
:
Aluminium, eloxiert
Dimensions (in mm)
:
135 x Ø 19,2
Measuring range
measuring range (Humidity)
:
0…10% rH
Measuring accuracy (humidity)
:
± 2%
measuring range (Temperature)
:
-40...+80°C
Measuring accuracy (temperature)
:
± 0,2°C
Signal output
:
0...10V | 4...20mA
EF 3…5 24 V
Conductive electrodes with 24 V DC direct connection
The conductive electrodes EF3...5 are approved by the "DIBt" as overfill prevention devices for liquids hazardous to water.
Properties
connection
:
integrierter Anschlusskopf
Protection class
:
IP 65
connection thread
:
G 1¼"
Material Screw connection
:
PPH
Material electrode rods
:
Edelstahl (1.4571), Hastelloy C, Titan, Tantal
material coating
:
PTFE
Coating length
:
voll = ganzer Stab (10 mm am Stabende sind blank) teil = ca. 250 mm von oben
Rod diameter
:
4 mm, 6 mm
rod length
:
max. 6 m
Operating temperature
:
85 °C
Operating pressure
:
atmosphärisch
Spacer
:
ab Länge > 1000 mm je 1000 mm 1 Abstandshalter
Properties electronic part
Operating temperature
:
–20...+85 °C
Storage temperature
:
–30...+85 °C
nominal voltage
:
24 V DC ± 15%
Power consumption
:
max. 2 W (Klemme A1, A2)
Switching voltage
:
max. 250 V AC, 150 V DC min. 5 V DC (Relais mit Kombi-Goldkontakten)
Switching current
:
max. 3 A AC, 3 A DC min. 1 mA
Switching capacity
:
max. 750 VA, 150 W
Sensitivity
:
3k ... 100 kΩ in vier Stufen (3 k, 10 k, 30 k, 100 kΩ) wählbar
ER-107
Electrode Relays with general approval for constructions Z-65.13-405, Z-65.40-191
Electrode relays for conductive level detection with approved design as part of an overfill cut-out device (Z-65.13-405) / leakage protection (Z-65.40-191)
Properties
details
:
folgen
ZT Serie
Reliable pressure measurement and optimum process monitoring with the ZT series
From low to high pressure and suitable for liquid and gaseous media.
Properties
Pressure type
:
Relativdruck | Absolutdruck
Housing
:
Edelstahl
Overpressure
:
1,5* fach bis 400 bar, darüber 1,2* fach
Bursting pressure
:
3* fach bis 600 bar, darüber 1,5* fach
Measurement parameters
response time
:
< 1 ms
Total error
:
≤ 0,5 % FS
Non-linearity
:
≤ 0,2 % FS
Non-repeatability
:
≤ 0,10 % FS
Hysteresis
:
≤ 0,15 % FS
ambient conditions
Temperature of the fluid
:
-40...+125 °C (0...+80 °C kompensierter Bereich)
Ambient temperature
:
-40...+105 °C
Storage temperature
:
-40...+125°C
Shock resistance
:
g 1000 gemäß IEC 60068-2-32
Vibration resistance
:
g 20 gemäß IEC 60068-2-6
TK-32X
Luminous Row Displays
Luminous row displays of type series TK-320...TK-322 are used for visually displaying process states such as filling levels.
Type
TK-320
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-321
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-322
:
19” Karteneinschub 7 TE, 3 HE
Properties
Protection class EN60529
:
IP 52
Operating temperature
:
– 20 °C...+60 °C
nominal voltage
:
24 V DC...230 V AC
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | Bürde max. 500 Ω
Relay
:
2 x Umschalter max. 230 V | min. 5 V | max. 3 A | min 1 mA
Display
Number of LEDs
:
33 (rot/grün); 32 (TK-322)
Resolution
:
ca. 3,5 %
Error
:
± 1 LED
connection
:
Schraubklemmen
connection TK-322
:
Steckerleiste
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | max. load 500 Ω
Relay(2xSwitch)
:
max. 230 V | min. 5 V
Relay(2xSwitch)
:
max. 3 A | min. 1 mA
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
Protection class EN60529
:
IP 65
connection thread
:
G1" | G1¼" | G1½"
Union nut
:
G2¾" | S 100x8
Operating temperature PE / PVC
:
atmospheric
Operating temperature PPH
:
90°C
Operating temperature PTFE
:
100°C
Operating pressure
:
atmospheric
Resistance value of line monitoring
: