Temperature sensor with CAN bus interface for air temperature measurement
CANopen transmitter for temperature measurement in media, semiconductor sensor
Properties
Measuring range
:
-40…+80 °C
deviation
:
± 0,3 K (10...80 °C)
Measuring element
:
Halbleiter-Diodenfühler
measuring resolution
:
0,1 K
measuring grid
:
ab 5 ms
ElectricalConnection
CAN protocol
:
CANopen 2.0 A, nach ciA DS 404
Physical Layer
:
nach DIN 11898
Operating voltage
:
10...48 V
Operating conditions
Operating temperature
:
-40...+80 °C
Storage temperature
:
-40°C...+120°C
Shock resistance
:
30g, Dauer: 14 ms bei Raumtemperatur
Vibration resistance
:
10g bei 20 bis 1000 Hz
Minimumairspeedrequiredformeasurementacrossthesensor
:
1,5 m/s
ZDS-H
Precision pressure switch for high-pressure applications up to 2,000 bar
Can be used in oil, brake fluid, diesel, air and other gases.
With very good stability and overpressure resistance.
Properties
Pressure range
:
0...2.000 bar gestuft
supply
:
24 V DC
Output
:
Relais 60 V AC/1A
overload
:
1,5 x Messbereich
Med. connection
:
G 1/4 Zoll
electrical connection
:
Schraubklemme
feature
:
Tasten, LCD-Anz.
ZMF-202e-IR
Robust propane gas sensor for industrial applications with extended operating temperature range and ATEX / SIL-2
The ZMF-202e-IR is a propane sensor for measuring propane concentration in harsh environments.
Properties
Operating conditions
:
-40 °C…+60 °C
Storage conditions
:
-40 °C…+85 °C
RelativeHumidity
:
0…95 % nicht kondensierend
Measurement method
:
NDIR (dual beam technology)
Certification
:
SIL2, ATEX
Signal output
:
4..20mA
Power supply
:
12…24 V DC
Housing
:
Edelstahl
Standard cable length
:
1,5 m
pressure conditions
:
800...1200 mbar
screw thread
:
M46x1,5
Measuring ranges
in ppm
:
in vol%
0...17.000ppm
:
0…1,7 vol% (100 % LEL)
0...21.000ppm
:
0…2,1 vol%
Options
Other cable lengths on request
:
ATEX certification (optional)
:
TK-32X
Luminous Row Displays
Luminous row displays of type series TK-320...TK-322 are used for visually displaying process states such as filling levels.
Type
TK-320
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-321
:
Schaltschrankeinbaugehäuse 24 x 96 mm
TK-322
:
19” Karteneinschub 7 TE, 3 HE
Properties
Protection class EN60529
:
IP 52
Operating temperature
:
– 20 °C...+60 °C
nominal voltage
:
24 V DC...230 V AC
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | Bürde max. 500 Ω
Relay
:
2 x Umschalter max. 230 V | min. 5 V | max. 3 A | min 1 mA
Display
Number of LEDs
:
33 (rot/grün); 32 (TK-322)
Resolution
:
ca. 3,5 %
Error
:
± 1 LED
connection
:
Schraubklemmen
connection TK-322
:
Steckerleiste
Input
:
0(4)...20 mA | 0(2)...10 V DC | 5...10kΩ
Output
:
4...20 mA | max. load 500 Ω
Relay(2xSwitch)
:
max. 230 V | min. 5 V
Relay(2xSwitch)
:
max. 3 A | min. 1 mA
FluidIX Lub-6
Inline-capable oil condition sensor based on a multi-channel infrared measuring cell for permanent monitoring of the oil condition and prevention of machine damage
Based on non-dispersive infrared technology (NDIR), ZILA GmbH has developed an inline-capable measuring system that permanently monitors the oil condition directly in the system. The optical measuring system consists of a multi-channel infrared measuring cell with associated electronics and peripherals.
General information
Housing
:
Robustes Aluminiumgehäuse
Operating voltage
:
18...36V DC (max. 400 mA @18V)
Dimensions
:
150 x 119 x 82 mm (L x B x H)
Operating conditions
Operating temperature:
:
0...+70 °C (optional 0...+90 °C)
Maximum operating pressure:
:
10 bar (optional 30 bar)
Storage temperature:
:
-40...+90 °C
Connection
ModBus TCP/IP
:
Ethernet-Port für Kommunikation über herstellerunabhängiges Busprotokoll
Digital I/O ports
:
1x Digital In 18...36V (10 mA max.), 4x Digital Out 18...36V (5 mA max.)
Operation
User Interface
:
grafisch über Weboberfläche im eingebundenen Netzwerk
Our application engineers advise you