Leakage probes with general building authority approval
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Connection
Box
:
Polyesterdose (PO)
Properties
Protection class
:
IP 65
Cable entry
:
PVDF-Verschraubung , PVC-Dichtung
Material Float
:
PE
Material leakage probe base
:
PE
Cable
:
TPK (PVC Basis)
Operating temperature
:
max. 60 °C
Operating pressure
:
atmosphärisch
media density
:
ρ ≥ 0,6 g/cm³
Switching hysteresis
:
typ. 2 mm
Switching point tolerance
:
max. 2 mm
Power supply
nominal voltage
:
24…230 V AC/DC
Power consumption
:
≤ 2 W
Output
Output contact
:
2 potentialfreie Wechselkontakte
Switching voltage
:
max. 250 V AC / 30 V DC
Switching current
:
max. 5 A AC / 5 A DC
Switching capacity
:
max. 750 VA / 90 W
displays
:
Betriebs-LED grün, Funktions-LED rot
Switching delay
:
ca. 0,5 s Anzug/Abfall
CE marking
:
siehe Konformitätserklärung
PVG-399
PVC weight with magnet insert and eyelet for cable fixing
for actuating monostable and bistable contacts
Variants
32
:
Außen Ø 25 mm x 175 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 32 u. 34 mm bis 6m Länge
37
:
Außen Ø 30 mm x 170 mm, Gewicht ca. 180 g, geeignet für Rohraußen Ø 40 mm bis 6m Länge
40
:
Außen Ø 40 mm x 110 mm ca. 175g, geeignet für Rohraußen Ø 50 mm bis 6m Länge
4012
:
Außen Ø 40 mm x 110 mm ca. 300g, geeignet für Rohraußen Ø 50 mm bis 12m Länge
4016
:
Außen Ø 40 mm x 110 mm ca. 360g geeignet für Rohraußen Ø 50 mm bis 16m Länge
50
:
Außen Ø 50 mm x 130 mm ca. 255g, geeignet für Rohraußen Ø 63 mm bis 6m Länge
5012
:
Außen Ø 50 mm x 130 mm ca. 300g geeignet für Rohraußen Ø 63 mm bis 12m Länge
5016
:
Außen Ø 50 mm x 130 mm, ca. 360g, geeignet für Rohraußen Ø 63 mm bis 16m Länge
TSL-CAN-03
Temperature sensor with CAN bus interface for air temperature measurement
CANopen transmitter for temperature measurement in media, semiconductor sensor
Properties
Measuring range
:
-40…+80 °C
deviation
:
± 0,3 K (10...80 °C)
Measuring element
:
Halbleiter-Diodenfühler
measuring resolution
:
0,1 K
measuring grid
:
ab 5 ms
ElectricalConnection
CAN protocol
:
CANopen 2.0 A, nach ciA DS 404
Physical Layer
:
nach DIN 11898
Operating voltage
:
10...48 V
Operating conditions
Operating temperature
:
-40...+80 °C
Storage temperature
:
-40°C...+120°C
Shock resistance
:
30g, Dauer: 14 ms bei Raumtemperatur
Vibration resistance
:
10g bei 20 bis 1000 Hz
Minimumairspeedrequiredformeasurementacrossthesensor
:
1,5 m/s
EK-CAN
PC program for CANopen sensors
Evaluation and configuration software for Fluid.iO CANopen sensors
Properties
Operating system
:
Windows
ltdata.BuildVersion
:
1.0.5 (28.10.2025)
installation type
:
ZIP, portable
ltdata.Sprache
:
DE | EN
EF2...5
Conductive Electrodes with general approval for constructions
Conductive electrodes type EF2...5 are approved by the “DIBt” (German Institute for Structural Engineering) as liquid level limit switches for the overfill protection of containers for storing water-endangering liquids
Properties
Protection class EN60529
:
IP 65
connection thread
:
G1" | G1¼" | G1½"
Union nut
:
G2¾" | S 100x8
Operating temperature PE / PVC
:
atmospheric
Operating temperature PPH
:
90°C
Operating temperature PTFE
:
100°C
Operating pressure
:
atmospheric
Resistance value of line monitoring
:
22 kΩ / 100 kΩ