Cart
LU-1X0 configure
TRM-100 configure
LU-1X0
Compact Ultrasonic Level Sensor
The LU-150 is a short-range integrated ultrasonic level transmitter, intrinsically safe as Ex-version LU-180. This general purpose, 2 wire, 4 to 20 mA loop powered transmitter is ideal for liquids, slurries, and bulk materials in open or closed vessels to 5 m (16.4 ft).
Properties
- Protection class EN60529 : IP 68
- Power supply : 12...30 V DC / 0.1A Spitze
- Power consumption : Max. 0,75 W (25 mA bei 24 V DC)
- Output : 4...20 mA
- Max. Load : 600 Ω bei 24 V DC
- Measuring span : Proportional oder umgekehrt proportional
- Measurable materials : Flüssigkeiten, Schlämme, Schuttgüter
- operating temperature : –20...+60 °C
- Opening angle : 12°
- working pressure : Atmosphärisch
- Display : 3-stelliges LCD
- Process connection : Gewinde G 2" (BSPP) EN 10226 PVDF
- Weight : 1,3 Kg
- Cable entry : Kabelverschraubung M 20 x 1.5
- Material housing electronics : Polybutylenterephthalat PBT
- Material sensor / thread : PVDF-Copolymer
Input
- Measuring range : 0,25...5,0 m
- frequency : 54 kHz
Measuring Accuracy
- Measurement deviation : ± 0,25 % vom Messbereich (in Luft)
- Resolution : 3 mm
- Temperature compensation : im Sensor integriert
- Echo processing : „Sonic Intelligence“ von Siemens
TRM-100
Turbidimeter (0...1.000 FNU or 500...4.000 FAU)
The turbidimeter TRM-100 is a compact device for measuring turbidity in liquids. The "turbidity" is measured using the scattered light method (angle 90 degrees) for the turbidity range of < 1,000 FNU (Formazine Nephelometric Units) and the transmitted light method (angle 0 degrees) for the turbidity ranges > 1,000 FAU (Formazine Attenuation Units).
Properties
- Operating pressure : max. 10 bar @ 20 °C | max. 2,5 bar @ 60 °C
- Measuring range : 500...4.000 FNU / FAU
- Measuring accuracy : +/-5 %
- Mounting position : horizontal
- Process connection : DN 20 | DN 40
- Flange connection : >= DN 20
- number of senders : 2
- number of receivers : 1
Material
- Seal : EPDM | optional FPM (Viton)
- Process connection : PVC | PPH
- Measuring tube : Borsilikatglas mit Nano Beschichtung
Input
- Power supply : 18...30 V DC
- Power consumption : < 2 W
Output
- Output contact : 4...20 mA
- Switching delay (adjustable) : 1...10 s
- Protection class : IP 65
- Switching voltage : max. 250 V AC | max. 115 V DC
- Switching current : max. 3 A
- Switching capacity : max. 500 VA, 60 Watt
- Potential-free changeover contact : 1 @ 1...10 s
TSL-CAN-03
Temperature sensor with CAN bus interface for air temperature measurement
CANopen transmitter for temperature measurement in media, semiconductor sensor
Properties
- Measuring range : -40…+80 °C
- deviation : ± 0,3 K (10...80 °C)
- Measuring element : Halbleiter-Diodenfühler
- measuring resolution : 0,1 K
- measuring grid : ab 5 ms
ElectricalConnection
- CAN protocol : CANopen 2.0 A, nach ciA DS 404
- Physical Layer : nach DIN 11898
- Operating voltage : 10...48 V
Operating conditions
- Operating temperature : -40...+80 °C
- Storage temperature : -40°C...+120°C
- Shock resistance : 30g, Dauer: 14 ms bei Raumtemperatur
- Vibration resistance : 10g bei 20 bis 1000 Hz
- Minimumairspeedrequiredformeasurementacrossthesensor : 1,5 m/s
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!