Cart
ZS-1 configure
TK-302 configure
XR-4x0 | XR-4x1 configure
HD-100 | HD-102 | HD-104 configure
MTA configure
ESE configure
T204-0.F
Immersible Magnetic Probe for Ex Zone 0 (Cat. 1)
The T20... magnetic immersion probes are used to detect fill level limits in containers for liquid media, where an explosive atmosphere of Zone 0 (Cat. 1) exists in the gas space above the liquid and an Ex-Zone 1 (Cat. 2) exists outside the container in the area of the junction box.
Properties
- connection : Kabel PUR blau
- Protection class : IP 68 Dose
- number of floats : max. 4x
- Operating temperature : max. 135 °C
- F-Contact : 1 / 12 kΩ
- Number of additional contacts : max. 3x Wechsler | 5x Schließer | 3x Öffner
- Switching current : 1 A, 2 A (nur mit Schirmung)
- Switching voltage : 230 V AC
Float
- Stainless steel ball 61 mm Ø : max. 20 bar | 0,65 g/cm³
- min. contact gap type 04 : 85 mm
Switching contacts and switching capacity
- Changeover contact : max. 3x | 60W/VA
- normally open : max. 5x | 100 W / VA
- Normally closed contact : max. 3x | 60 W/VA
ZS-1
Differential pressure sensor for low pressure
Compact and robust differential pressure transmitter for measurement on air and other non-aggressive media
Properties
- Pressure type : Differenzdruck
- Housing : Aluminium
- medium : Luft und nicht aggressive Gase
Measurement parameters
- response time : < 2,5 s
- Hysteresis : 0,1 %
- Overload capacity : 4* fach bis 500 mbar, darüber 2* fach
- Signal output selection : 0...10 V | 4...20 mA, 2-Leiter
Operating conditions
- Operating voltage : 24 VDC/AC ±10 % (0...10 V) | 15...30 VDC (4...20 mA)
- Operating temperature : -20...+50 °C
Connections
- Electrical connection : Schraubklemme im Gehäuse
- Process connection : Schlauchanschluss 4 mm oder 6 mm
- Cable gland : PG 7
Pressure measuring range
- 0...0,25mbar :
- 0...0,5mbar :
- 0...1mbar :
- 0...2,5mbar :
TK-302
Level transducer made of brass and stainless steel
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
- connection : Dose
- Protection class socket / plug : IP 65
- Protection class EN60529 cable : IP 55
- Float type : 03 (04)
- connection cable : 1000 mm Silikon 0,5 mm²
- Sliding tube length : max. 6000 mm
- Operating temperature : max. 130 °C
- Operating pressure : max. 20 bar
- Resolution : 10 mm | 15 mm | 1 % | 2 % | 5 %
- Accessories : R/I-Wandler TK-101
MaterialDensity
- Type 03 : 0,75 g/cm³
- Type 04 : 0,65 g/cm³
ER-Serie
Electrode Relays
Electrode relays for conductive level detection for all areas in which conductive, liquid media are to be detected, controlled or monitored
Properties
- details : folgen
T200.F
Overfill protection for containers
Level sensors type T-20_.F... are
approved by the DIBt (German
Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Connection
- Polyester junction box :
- Aluminum housing :
- Polyethylene connection head :
- Cable :
- Plug :
Properties
- Protection class EN60529 : IP 65
- connection thread : G 1", G 1¼", G 1½", G2", G3”
- Union nut : G 2¾", S 100x8
- Guide tube length : max. 6 m
- Operating pressure : Max. 20 bar
- media density : ρ ≥ 0,6 g/cm³
- Switching hysteresis : typ. 2 mm
- Switching point tolerance : max. 2 mm
- Operating temperature : atmosphärisch
- PP : max. 90°C
Resistance value
- Operational readiness : ca. 1 kΩ
- overfill alarm : ca. 12 kΩ
- Switching time : ca. 20 ms
- ltdata. :
XR-4x0 | XR-4x1
Electrode relay with ATEX
The electrode relays are used for conductive level detection.
levels. The possible applications extend
areas where conductive, liquid media are to be detected, controlled
to be detected, controlled or regulated. Hereby
level detection (overflow / dry run) as well as minimum / maximum
as well as minimum / maximum controls can be realised.
Protection class EN60529
- clamp : IP20
- Housing : IP40
Technical Data
- Operating temperature : -20...+60 °C
- Storage temperature : -30...+80 °C
- Output contacts : potentialfrei
- Switching voltage : min. 5 V | max. 250 V AC / 150 V DC
- Switching current : min. 5 mA | max. 5 A AC / 5 A DC
- Switching capacity : min. 300 mW | max. 100 VA / 50 W
- Quiescent current : umschaltbar
- Weight : ca. 250 g
- CE marking : siehe Konformitätserklärung
- Ex-protection/IECEx : siehe Prüfbescheinigung
HD-100 | HD-102 | HD-104
Hydrostatic immersion probes (0.8...10mWS)
Continuous and precise level measurement in unpressurised, open basins and tanks as well as underground applications such as shafts, wells and boreholes.
Properties
- Protection class EN60529 : IP68
- Operating temperature : -10...70 °C (PVC: -10...60 °C)
- Storage temperature : -25...70 °C (PVC: -10...60 °C)
- Power supply : 15...30 V DC
- power : max. 25 mA
- Output : 2-Leiter-Technik
- Measuring range : 0,8...10 mWs (Standard)
- Overpressure : abhängig vom Messbereich
- Deviation from characteristic curve : Nichtlinearität,
- Insulation resistance : > 100 kΩ
- Short-circuit resistance : permanent
- Reverse polarity protection : keine Schädigung o. Funktion bei vertauschten Anschlüssen
Materials
- Housing : Edelstahl 1.4571, PVC, PVDF
- Measuring cell : Edelstahl 1.4404, Keramik Al2o3 96%, Keramik Al2o3 99,9%
- Seals : FKM (Viton ®), EPDM, FFKM (Kalrez ®)
- Cable : PVC, PUR, FEP (Ø8 mm; 2 x 0,25 mm2 mit Luftschlauch und PTFE-Filter
MTA
Mechanical tank level indicator
The tank level indicator is a mechanically actuated indication operating "on the spot”. It permits a high degree of safety and flexibility thanks to separate points of measurement and indication.
Properties
- Tank connection : Flansch ab DN 80 (Sonderanschlüsse auf Wunsch)
- Material : siehe Maßbild
- Material Tube : PVC, transparent | Ø 50 x 1,8 | Ø 63 x 3,0
- Operating temperature : –20...+60 °C
- Operating pressure : atmosphärisch
Material Float
- PPH : Ø 70 mm 460 g
- PVC : Ø 70 mm 455 g
- PPH : Ø 40 mm 370g
- PE : Ø 70 mm ca. 450 g
Material Rope
- PPH : (rot, Ø 2 mm) ~ 2 g/m
- Polyester : (bunt, Ø 2 mm) ~ 4 g/m
- PTFE : (weiss, Ø 3 mm) ~ 10 g/m
ESE
Switching channel extension for ES series
TÜV-certified, type-tested electronic safety switching device (SIL2)
Properties
- Operating voltage : 16...32 V DC (max. 5,9 W)
- Dimensions : 150 x 60 x 42 mm (L x B x H)
- Housing : Aluminium (eloxiert)
- Protection class : IP65
Approvals
- DGRL 2014/68/EU Kat:IV : Baumustergeprüft gemäß Druckgeräterichtlinie
- DIN EN12263:1998 : Kälteanlagen und Wärmepumpen Sicherheitsschalteinrichtungen zur Druckbegrenzung -Anforderungen und Prüfungen; Kategorie IV
- DIN EN378:2020 : Kälteanlagen und Wärmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen
- DIN EN61508:2011 : SIL2
Measuring ranges
- Measuring range relative pressure (nominal pressure) : -1…500 bar
- Measuring range differential pressure (nominal pressure) : 0…1 mbar - 0…1.000 mbar
- Setting accuracy (from nominal pressure) : 0,1 %
Operating conditions
- Pressure type : Relativdruck, Differenzdruck
- Temperature of the fluid : -40…+125 °C
- Ambient temperature : -20…+65 °C
- Parts in contact with media : Edelstahl
process connection
- Version relative pressure : G ¼“ Innengewinde
- Version differential pressure : G ⅛“ Innengewinde
- Adapter for process connection : 6mm; 8mm oder 10mm
electrical connection
- Analogue current output : 1x 4…20 mA
- Digital inputs/outputs : 2x Alarm oder 1x Alarm & 1x Fernentriegelung
Load capacity of the switching contacts DC (24V)
- DC1 : 16 A
- DC13 : 1,5A
Load capacity of the switching contacts AC (230V)
- AC1 : 16 A
- AC3 : 10 A
- AC15 : 7 A
Our application engineers advise you personally, comprehensively and professionally!
Simply contact us by phone or e-mail!