The TK-312 measuring transducer converts the resistance signal supplied from a continuous level sensor into a current signal proportionate to the level.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel housing
:
IP 40
Operating temperature
:
–20...+60 °C
nominal voltage
:
24... 230 V AC/DC
Power consumption
:
2 VA, 2W
Dimensions housing type B
:
22,5 x 114,5 x 99
Dimensions housing type C
:
22,5 x 114,5 x 114
Input
Voltage
:
0...10 V
Resistance in three-wire circuit RG
:
0-4...10 kW
Output
Temperature influence tolerance
:
max. ± 0,6 % der Signalspanne
Current output
:
0/4... 20 mA bezogen auf die Masse des Eingangs
Voltage output
:
0/2... 10 V
Mounting
:
Tragschiene nach EN 50022
Weight
:
175 g
TK-308
Liquid Level Measuring Instruments Series
T30... continuous magnetic immersible probes are used for quasi-acquisition of the filling level in containers with liquid media.
Technical Data
Protection class socket / plug
:
IP 65
Protection class EN60529 cable
:
IP 55
Float type
:
11,12, 15, 17
connection cable
:
1000 mm LiYY 0,5 mm² oder Silikon 0,5 mm²
Sliding tube length
:
max. 6000 mm
Operating pressure
:
max. 6 bar
Resolution
:
7,5 mm | 10 mm | 15 mm | 20 mm | 1 % | 2 % | 5 %
Accessories
:
R/I-Wandler TK-101
Operating temperature
PVC
:
max. 60 °C
PE
:
max. 80 °C
PP
:
max. 90 °C
MaterialDensity
Type 11
:
0,60 g/cm³
Type 12
:
1,00 g/cm³
Type 15
:
0,59 g/cm³
Type 17
:
0,63 g/cm³
AD-310
programmable Digital Display
The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Properties
Protection class EN60529 clamp
:
IP 20
Protection class EN60529 front panel
:
IP 65
Operating temperature
:
– 20...+ 60 °C
nominal voltage
:
Weitbereichsnetzteil; 20 V DC ... 230 V AC
Power consumption
:
max. ca. 3 VA
Output contact
:
2 Schließer / NO
Switching voltage
:
max. 250 V AC, 300 V DC
Switching current
:
max. 3 A , DC min. 30 mA
Switching capacity
:
max. 50W, 100 VA
Unregulated auxiliary voltage source
:
15...20 V DC / 20 mA
Display
:
LED 14 mm, 5-stellig
Dimensions
:
96x48x100 mm
Weight
:
ca. 200 g
Panel cut-out
:
H:45+0,6mm, B:92+0,8 mm
Equipment
Measuring input current
:
0(4)...20 mA DC
Measuring input voltage
:
0(2)...10 V DC
Measuring input Potentiometric voltage divider
:
1...100 kΩ
Display
:
LED 14 mm, 5-stellig
operation
:
Folientasten
Display range
:
-19999...32000
data backup
:
EEPROM
measurement uncertainty
:
±1 % oder ±1 Digit
analogue output
:
0 (4)...20 mA
Our application engineers advise you